AirStage ASUB30TLAV1 Kurulum Kılavuzu - Sayfa 12
Klima AirStage ASUB30TLAV1 için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. AirStage ASUB30TLAV1 16 sayfaları.
6.1. Setting the address
Manual address setting method
The indoor unit address and the refrigerant circuit address can also be set up through the
wireless remote controller
Be sure to turn OFF the power before performing the field setting.
• Position and detail of the switches
4/7/9 model
In the 4/7/9 models, you need to remove
the front panel. Refer to "8. FRONT PANEL
REMOVAL AND INSTALLATION".
4/7/9 model
For refrigerant
circuit address
For indoor unit
address
• Please set it according to the following procedures when setting manually.
Use an insulated screwdriver to set the dip switches.
Be careful not to make mistakes for switch settings.
6.1.1 Indoor unit address
• Rotary switch (IU AD × 1)....Factory setting "0"
• Rotary switch (IU AD × 10)....Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD
SW as shown in the Table A
6.1.2 Refrigerant circuit address
• Rotary switch (REF AD × 1)....Factory setting "0"
• Rotary switch (REF AD × 10)....Factory setting "0"
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A for
each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
Setting
Setting range
Indoor unit
0 to 63
address
Refrigerant
0 to 99
circuit address
• If working in an environment where the wireless remote controller can be used, the ad-
dresses can also be set using the remote controller.
• If setting the addresses using the wireless remote controller, set the indoor unit address
and refrigerant circuit address to "00".
(For information on setting using the wireless remote controller.)
En-11
CAUTION
30/36 model
30/36 model
For indoor
For refrigerant
unit address
circuit address
IU AD
REF AD
×10
×1
×10
×1
SET3
SET4
CAUTION
Type of switch
Setting
example 2
IU AD × 10
Setting
example 63
REF AD × 10
REF AD × 1
Table A
Address
Refrigerant circuit
0
1
2
3
4
5
6
7
8
9
10
11
12
.
.
.
99
Do no t set the indoor unit address (IU AD SW) at 64 to 99. It may result in failure .
6.2. Custom code setting
• Selecting the custom code prevents the indoor unit mix-up. (figure below)
(Up to 4 codes can be set.)
• Perform the setting for both the indoor unit and the remote controller.
Indoor unit
Remote
controller
• Custom code setting for indoor unit
RC AD
Set the DIP switch SET3 SW1, 2, referring to the figure and table below.
DIP switch "SET3"
ON
OFF
SW
6.3. Function setting
Please make this setting after completing all construction works.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
IU AD × 1
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "6.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Filter
indicator
interval
Filter
indicator
action
(Forbid-
den)
Rotary Switch Setting
REF AD SW
Indoor unit
× 10
× 1
0
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
1
0
1
1
1
2
.
.
.
.
.
.
9
9
Confusion
4/7/9 model
DIP switch
"SET3"
DIP switch
SET3
SW1
SW2
SW
SW
SW
1
2
3
4
WARNING
Setting number
Default
00 Standard
01 Longer
11
02 Shorter
00 Enable
01 Disable
13
Display only
on central
02
remote
controller
23
00
Address
Rotary Switch Setting
IU AD SW
× 10
× 1
0
0
0
1
0
1
2
0
2
3
0
3
4
0
4
5
0
5
6
0
6
7
0
7
8
0
8
9
0
9
10
1
0
11
1
1
12
1
2
.
.
.
.
.
.
.
.
.
63
6
3
Code change
A
B
C
D
A
B
C
D
30/36 model
IU AD
REF AD
RC AD
×10
×1
×10
×1
SET3
SET4
DIP switch "SET3"
Custom code
A (Factory
B
C
D
setting)
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Details
Adjust the filter cleaning interval
notification. If the notification is too
early, change to setting 01. If the
notification is too late, change to
setting 02.
Enable or disable the filter indica-
tor. Setting 02 is for use with a
central remote controller.