Function
Function
Setting number
number
00
Super low
Cool Air
43
Follow the setting
Prevention
01
on the remote
controller
00
Start/Stop
01 Emergency stop
External
46
control
02
Forced stop
00
All
Error report
47
Display only on
target
01
central remote
controller
Follow the setting
00
on the remote
Fan setting
controller
when cooling
49
thermostat
OFF
01
Stop
Mode 0
00
Mode 1
01
Switching
Mode 2
02
functions
Mode 3
03
for external
Mode 4
inputs and
60
04
external
Mode 5
05
outputs
Mode 6
06
terminals
Mode 7
07
Mode 8
08
Auxiliary heater
00
control 1
Auxiliary heater
01
control 2
Heat pump pro-
02
Control
hibition control
switching
Heater selection
61
of external
control using
03
heaters
outdoor tempera-
ture 1
Heater selection
control using
04
outdoor tempera-
ture 2
00
Setting 0
01
Setting 1
Operating
temperature
02
Setting 2
switching
62
03
Setting 3
of external
heaters
04
Setting 4
05
Setting 5
Temperature conditions when the external heater is ON
Temperature (t) when the external heater is ON= Room temperature - set temperature
00
00
t < -5.4°F (-3°C)
01
t < -3.6°F (-2°C)
02
t < -3.6°F (-2°C)
03
t < -5.4°F (-3°C)
04
t < -7.2°F (-4°C)
05
t < -9.0°F (-5°C)
Default
Details
Restrain the cold airfl ow with
making the airfl ow lower when
starting heating operation. To
correspond to the ventilation,
set to 01.
Allow an external controller to
start or stop the system, or to
perform an emergency stop.
* If an emergency stop is
performed from an external
controller, all refrigerant
systems will be disabled.
* If forced stop is set, indoor
unit stops by the input to
the external input terminals,
and Start/Stop by a remote
controller is restricted.
Change the target for report-
ing errors. Errors can either be
reported in all locations, or only
on the wired remote.
When set to 01, the fan stops
when the thermostat is OFF in
cooling operation. Connection
of the wired remote controller
(2-wire type or 3-wire type)
and switching its thermistor are
necessary.
• Set this function when connect-
ing the VRF system to a venti-
lator, economizer, humidifi er, or
other external device.
• The connection terminal func-
tions can be changed depend-
ing on the type of external
device. For details of the con-
nection terminal functions, see
the Design & Technical Manual.
Sets the control method for the
external heater being used. For
details of the control method,
see the Design & Technical
Manual.
• Sets the temperature conditions
when the external heater is ON.
• For the temperature conditions,
see "Temperature conditions
when the external heater is
ON". For a more detailed
explanation, see the Design &
Technical Manual.
Set value of function: 61
01
02
03
t ≤ -0.9°F (-0.5°C)
t ≤ -1.8°F (-1°C)
t ≤ -3.6°F (-2°C)
t ≤ -5.4°F (-3°C)
t ≤ -7.2°F (-4°C)
t ≤ -9.0°F (-5°C)
7.3.1. Button name and function
7.3.2. Checking the function settings
• Press and hold the "MANUAL AUTO" button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to
normal operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
OPERATION indicator lamp
(Green)
TIMER indicator lamp (Orange) Address: tens place (0.5s ON/0.5s OFF)
FILTER indicator
lamp (Red)
• Indoor unit address example
(Example) ADDRESS : 24
OPERATION
ON
indicator lamp
(Green)
OFF
ON
TIMER
indicator lamp
(Orange)
OFF
ON
FILTER
indicator lamp
OFF
(Red)
• Refrigerant address example
(Example) ADDRESS : 30
OPERATION
ON
indicator lamp
(Green)
OFF
TIMER
ON
indicator lamp
(Orange)
OFF
ON
FILTER
04
indicator lamp
(Red)
OFF
• Setting details
Function number
01
02
For use with a remote controller, set all rotary switches to 0, and refer to "7.1. Setting the
address" for details.
All switches are set to 0 at the factory.
FILTER indicator
lamp (Red)
TIMER indicator
lamp (Orange)
OPERATION indicator
lamp (Green)
MANUAL AUTO
button
(Optional)
Indication pattern
Indoor unit address
Refrigerant address
ON
Flash (1.0s ON/1.0s OFF)
Address: ones place (0.5s ON/0.5s OFF)
1 cycle 12 sec
ON
0.5s 0.5s 0.5s 0.5s
10 sec
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
8 sec
1 cycle 12 sec
1.0s
1.0s
1.0s
1.0s
1.0s
1.0s
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
9 sec
OFF
Item
Setting number
Indoor unit address
Refrigeration address
1.0s
00 to 63
00 to 99