When switching the DIP switch (SW1), be sure to turn off the power supply to the
indoor unit. Otherwise, the PC board of the indoor unit may be damaged.
X1, X2:
Transmission cable
Cable tie (Medium)
(Accessories)
Remote controller
cable
For 2-wire type
Y1: Non-polar
Connect the remote
Y2: Non-polar
controller cable
Y3: Do not connect *1
Set the DIP switch (SW1)
2WIRE (Factory setting)
*1: If you connect the remote controller cable to the terminal Y3, 2-wire type
remote controller does not work.
(3) Please fi x the Connection cable with cable Clamp. And then install the Wire Cover with
screws.
(4) Install control box cover.
Do not bundle the remote controller cable, or wire the remote controller cable in
parallel, with the indoor unit connection wire (to the outdoor unit) and the power
supply cable. It may cause erroneous operation.
CAUTION
Cable clamp
L, N:
Power supply
cable
2WIRE
DIP switch (SW1)
3WIRE
SW1
For 3-wire type
Y1: Red
Y2: White
Y3: Black
3WIRE
(c)
Bind securely
Detail (c)
CAUTION
1
6.5. External input and external output (Optional
parts)
Controller PCB
Apply voltage terminal
(CNA03)
(CNA01)
Output terminal
(CNB01)
Dry contact terminal
(CNA02)
(1) External input
• Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit
PCB CNA01 or CNA02.
• "Operation/Stop" mode, "Emergency stop" mode or "Forced stop" mode can be selected
with function setting of indoor unit.
• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
● Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
DC power supply
12 to 24V
Load
resistance
*a
Load
resistance
*a
Load
resistance
*a
connected unit
*1 Make the power supply DC12 to 24V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
When connected to Apply voltage terminals of multiple indoor units with a connected unit,
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
DC power supply
12 to 24V
Load
resistance
Load
resistance
connected unit
DIP switch
(SET 2)
OFF
ON
SW1
SW2
SW3
SW4
(CNA04)
*1
P.C.B
CNA01
*b
CNA03
P.C.B
CNA01
P.C.B
CNA01
P.C.B
CNA01
En-10