AirStage AUXB18GALH Kurulum Kılavuzu - Sayfa 4
Klima AirStage AUXB18GALH için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. AirStage AUXB18GALH 16 sayfaları. Indoor unit (cassette type)
Ayrıca AirStage AUXB18GALH için: Kullanım Kılavuzu (6 sayfalar)
Decide the mounting position with the customer as follows:
(1) Install the indoor unit on a place having a suffi cient strength so that it withstands
against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) A place from where the air can be distributed evenly throughout the room by the unit.
(5) Install the unit where connection to the outdoor unit (or RB unit) is easy.
(6) Install the unit where the connection pipe can be easily installed.
(7) Install the unit where the drain pipe can be easily installed.
(8) Install the unit where noise and vibrations are not amplifi ed.
(9) Take servicing, etc., into consideration and leave the spaces. Also install the unit
where the fi lter can be removed.
3.2. Installation dimensions
• Leave the space specifi ed in Fig. A so that the air from the blower will cover the entire
room.
• Install the indoor unit on a place having a suffi cient strength so that it withstands
against the weight of the indoor unit.
• A place from where drainage can be extracted outdoors easily.
Never install in a room where there is the potential of leaking fl ammable gas. A spark
could ignite the gas and cause an explosion or fi re.
Avoid installing in a location with high temperature.
Fig. A
Strong and durable ceiling
Obstruction
Floor
The maximum height from fl oor to ceiling
Model name
AUXB07
AUXB09
Default mode
2,700
(Standard mode)
High Ceiling
-
mode
* Be sure to make the function settings with the remote controller according to the
installed ceiling height.
3.3. Discharge direction setting
• The discharge direction can be selected as shown below.
Fig. B
(4 directions)
En-3
WARNING
262 mm
or more
1,000 mm
or more
H (mm)
AUXB12
AUXB14
AUXB18
2,700
2,700
2,700
2,700
-
3,000
3,000
3,000
100 mm or more
(3 directions)
Piping position
* Select the most appropriate airfl ow direction from 3 or 4 directions according to the
shape of the room and the installation position.
* When changing the number of outlets, we recommend using the optional AIR OUTLET
SHUTTER PLATE KIT to close the outlet.
* For the specifi c closing pattern, please refer to the attached AIR OUTLET SHUTTER
PLATE KIT'S MANUAL. (Do so before installing the cassette grille as it will be installed
on the body.)
3.4. Installing the unit
Install the air conditioner in a location which can withstand a load of at least 5 times the
weight of the main unit and which will not amplify sound or vibration. If the installation
location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please take care.
When fastening the hangers, make the bolt positions uniform.
Perform fi nal tightening by tightening the double nut fi rmly. The product may fall if not
installed properly.
Using a level, or vinyl hose fi lled with water, fi ne adjust so that the body is level.
Install the air conditioner as follows.
INDOOR UNIT INSTALLATION
(1) Make the holes for installing in the ceiling (Fig. D).
(2) Install the hanging bolts (M10), refer to the position in Fig. C.
(3) Install special nut A, then special nut B onto the hanging bolt (Fig. D).
(4) Raise the body and mount its hooks onto the hanging bolt between the special nuts.
(5) Turn special nut B to adjust the height of the body.
(6) Be sure to leave service access for future service at the designated position.
Fig. C
AUXB24
2,700
3,000
Fig. D
102 mm
Ceiling
WARNING
530 mm (Hanging bolt position)
135 mm
250 mm
Service access
Min. 450 mm
Drain pipe (O.D. ø25.4)
99 mm
40 mm
Control box
Gas pipe
Liquid pipe