6.4. Connection of wiring

(1) Remove the control box cover and wiring cover by loosening the screws.
Wiring
connect-
ing port (for
transmission cable
and remote controller
cable)
(2) Thread each cable through the holes or indents of the cabinet and connect the wires.
(3) After wiring is complete, secure the cables with the cable clamps.
Push mount cable tie (accessories)
Wiring connecting port
(for power supply cable)
Wiring cover
Control box cover
Earth
(ground)
Cable
clamp
Power supply cable
X1, X2: Transmission cable
Cut
Y1, Y2: Remote controller cable
(do not use Y3.)
(4) Replace the Control box
cover and Wiring cover.
Securely tighten the
screws.
Cure the wiring connecting
port and remote controller
connecting port with putty or
heat insulation so that insects
or dust will not enter the unit.
Do not bundle the remote controller cable, or wire the remote controller cable in parallel,
with the indoor unit connection wire (to the outdoor unit) and the power supply cable. It
may cause erroneous operation.

6.5. External input and external output (Optional parts)

Output terminal
Apply voltage terminal
CNB01
CNA01
CNA03
CNA02
CNA04
Dry contact terminal
6.5.1 External input
• Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit
PCB CNA01 or CNA02.
• "Operation/Stop" mode, "Emergency stop" mode or "Forced stop" mode can be selected
with function setting of indoor unit.
• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
● Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
DC power supply
12 to 24V
Load
resistance
*a
Load
resistance
*a
Load
resistance
*a
Connected unit
*1: Make the power supply DC 12 to 24 V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24 V across pins 1-2, and 1-3.
*a: The allowable current is DC 5 mA to 10 mA. (Recommended: DC 5 mA)
Provide a load resistance such that the current becomes DC 10 mA or less.
Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*b: The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
CAUTION
Controller PCB
SET 2
ON
DIP switch
OFF
(SET 2)
SW1
SW3
SW2
SW4
P.C.B
*1
CNA01
*b
CNA03
En-8