CARLO GAVAZZI PPB01 Manuel - Sayfa 2
Röleler CARLO GAVAZZI PPB01 için çevrimiçi göz atın veya pdf Manuel indirin. CARLO GAVAZZI PPB01 4 sayfaları. Monitoring relays
Ayrıca CARLO GAVAZZI PPB01 için: Kullanım Kılavuzu (8 sayfalar)
DPB01, PPB01
Supply Specifications
Power supply
Rated operational voltage
through terminals:
L1, L2, L3, N
(DPB01)
5, 6, 7, 11
(PPB01)
M23 - Delta Voltage:
M48 - Delta Voltage:
M48 - Star Voltage:
Rated operational power
DPB01CM23, PPB01CM23
DPB01CM48, PPB01CM48
Mode of Operation
Connected to the 3 phases
(and neutral) DPB01 and
PPB01 operate when all 3
phases are present at the
same
time,
the
phase
sequence is correct (not
DPB01...N and PPB...N) and
the phase-phase (or phase-
neutral) voltage levels are
within set limits.
If one or more phase-phase
or
phase-neutral
voltages
exceeds the upper set level
or drops below the lower set
2
Overvoltage cat. III
(IEC 60664, IEC 60038)
208 to 240 VAC ± 15%
45 to 65 Hz
380 to 480 VAC ± 15%
45 to 65 Hz
220 to 277 VAC ± 15%
45 to 65 Hz
13 VA @ 230 ∆VAC, 50 Hz
13 VA @ 400 ∆VAC, 50 Hz
Supplied by L1 and L2
level, the red LED starts
flashing 2 Hz and the output
relay releases after the set
time period. In any case if
phase-neutral measurement
is
selected
both
phase-
phase
and
phase-neutral
voltages are monitored. If the
phase sequence is wrong or
one phase is lost, the output
relay releases immediately.
Only 200 ms delay occurs.
The failure is indicated by the
red LED flashing 5 Hz during
the alarm condition.
General Specifications
Power ON delay
Reaction time
Incorrect phase sequence or
total phase loss
Voltage level
Alarm ON delay
Alarm OFF delay
Accuracy
Temperature drift
Delay ON alarm
Repeatability
Indication for
Power supply ON
Alarm ON
Output relay ON
Environment
Degree of protection
Pollution degree
Operating temperature
@ Max. voltage, 50 Hz
@ Max. voltage, 60 Hz
Storage temperature
Housing dimensions
DIN-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
Approvals
CE Marking
EMC
Immunity
Emissions
Example 1
(mains network monitoring)
The relay monitors over and
under voltage, phase loss
and correct phase sequence.
In case of DPB01...N or
PPB01...N, the relay moni-
tors over and under voltage.
Specifications are subject to change without notice (09.05.05)
1 s ± 0.5 s or 6 s ± 0.5 s
< 200 ms
(input signal variation from
-20% to +20% or from
+20% to -20% of set value)
< 200 ms (delay < 0.1 s)
< 200 ms (delay < 0.1 s)
(15 min warm-up time)
± 1000 ppm/°C
± 10% on set value ± 50 ms
± 0.5% on full-scale
LED, green
LED, red (flashing 2 Hz
during delay time)
LED, yellow
IP 20
3 (DPB01), 2 (PPB01)
-20 to 60°C, R.H. < 95%
-20 to 50°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
22.5 x 80 x 99.5 mm
36 x 80 x 94 mm
Approx. 120 g
Max. 0.5 Nm
according to IEC 60947
UL, CSA
Yes
Electromagnetic Compatibility
According to EN 61000-6-2
According to EN 50081-1
Example 2
(load monitoring)
The relay releases in case of
interruption of one or more
phases, when one or more
voltages drop below the low-
er set level or exceed the
upper set level.