Athena 6200 Kullanım Kılavuzu - Sayfa 4
Sıcaklık Kontrolörü Athena 6200 için çevrimiçi göz atın veya pdf Kullanım Kılavuzu indirin. Athena 6200 16 sayfaları. Microprocessor-based temperature controller
Front Panel Adjustments
Touch Key
Index: Allows the following adjustments to be selected.
1) set point temperature
2) alarm one temperature setting
3) alarm two temperature setting
4) rate with tracking reset (1:6ratio)
5) heat gain
6) heat cycle time
7) cool gain
6) cool cycle time
up/down keys: increases/decreases values of above adjustments
Enter:
writes selected values to nonvolatile memory
Internal switches/jumpers
A) 4 position dip switch
1) selects ºF/°C display
2) selects energized alarm two on hi/low (dev + / dev -) temperature
3) selects energized alarm one on hi/low (dev + / dev -) temperature
4) selects process or deviation alarm function
B) 2 position dip switch
1) selects reduced rate gain
2) locks out front panel parameter entry excepting set point
NOTES: *** setting to zero disables output
* setting to zero initiates 60 millisecond timebase for ultra fast cycling.
Use with external solid state relays.
**Setting to zero disables reset and rate actlon for proportional only control.
To order see price sheet C-5-82
General
Congratulations on purchasing an outstanding
temperature controller Ingenious use of
microprocessor technology has given you an
economical, compact controller that:
Accurately measures, linearizes and displays
1.
temperature in º F and º C .
2.
Digitally enters and displays control and alarm set
points as well as heat and cool gains, cycle times,
and user simplified rate and reset action.
Can be switched configured for high and low
3.
process alarms or deviation alarms.
4.
Can be field converted from relay output "B", to
solid state relay "T" to solid state relay driver "S"
or to a 4-20 MA output SCR driver "F", with
independent outputs for heat and cool.
Will remember its "entered" settings after power
5.
failure or shut-off and not "Go To Sleep".
CAUTION: HIGH VOLTAGE AND HIGH TEMPERATURES CAN
CAUSE INJURY AND ARE A FIRE HAZARD. PLEASE READ
ALL INSTRUCTIONS, HAVE ONLY SKILLED PROFESSIONALS
WIRE THE UNIT, AND USE AN APPROVED TEMPERATURE
AND/OR PRESSURE SAFETY CONTROL. EVEN THE BEST
COMPONENTS CAN BE DAMAGED OR MAY NOT FAIL SAFE.
4
0 to span
0 to span
0 to span
** 0 to 120 sec
*** 1 to 400
* 1 to 120 sec
*** 1 to 400
x