5. Basic functions

5-1 Function of code setting
Function code Name of function
Setting range
Factory value
30-70%
Starting voltage
2-60S
Time of soft start
0-60S
Time of soft stop
Time delay
0-999S
starting
Time delay
0-999S
programming
Time delay
0-999S
interval
Current limiting
50-500%
when starting
Max working
50-200%
current
Display mode of
00-03
the keyboard
Under-voltage
40-99%
protection
Over voltage
100-130%
protection
00-06
Starting mode
Allowed output
00-04
protection
Operating control
00-07
mode
00-09
Allowed restart
Allowed parameter
00-03
modify
Communication
00-64
address
Programming
00-07
output
Current limiting
20-100
when soft stop
Aircraft
Motor rated
current
Settings
Motor underload
00-99%
protection
00-11
Bypass Delay
Remark: 1. The max working current whose code is P7 means the max current for motor's conti-
nuous operation on the basis of PP setting value.
2. If you do not press the operating keys when under the setting state, then it will exit
the setting state automatically.
3. It is unable to set any parameter during soft start and soft stop, and you can set under
any other state.
Description
Effective under voltage ramp mode; when PB is set at 1,
it is modifiable, and set at 0, the starting voltage is 40%
Effective under voltage ramp mode; when code PB
is set 1, the modification is effective
Free parking is set to 0, 1 drag N should be set to 0
Press starting key (set the time), time delay starting
by count down, set at 0, it will start immediately
Output (03 and 04 terminals) of the relay, set at 0,
it will close immediately
Time delay when release from overheat, the
indication lamp flashes during the time delay
Effective under current limiting mode; when code
PB is set at 0, the modification is effective, and set
at 1, the max current limiting value 400%
The input mode of parameter P6 and P7 is
determined by P8
Refer to 6-1 in Page 12 for details
Protect when it is lower than the set value
Protect when it is higher than the ser value
00 current-limit; 01 voltage; 02 kick +current-limit;
03 kick +voltage; 04 current ramp; 05 double closed loop;
06 forbidden
00 primary; 01 light load; 02 standard;
03 heavy load; 04 senior
When set at 0, it is keyboard operation,
refer to 6-2 in Page 12 fore details
0: forbidden; 01-09: times of automatic restart
00: not allowed to modify the parameter;
01:allowed to modify the part of purameter;
02: allowed to modify the parameter
03: Allows modification bypass delay
Used for multi soft starters and upper machine for
multi-machine communication
Output setting (03 and 04 terminals) of relay,
refer to 6-4 in Page 12
Refer to description in P21
The soft start showing adaptation of the motor
rated current
Refer to 6-4 in Page 12 for details
When PF is 03 Visible
-11-

6. Instruction for function selection

6-1 Code P8 is used to choose input mode and display mode
The set value of code P8
Input mode of P6 and P7
Current value Percent

Display mode

Current value Current value
■When code P6 and P7 input by percent, it indicates the percent of current value of the motor set by code FP.
6-2 Code PD is used to choose control mode of the soft starter
Value of PD
Keyboard control
Terminal control
Communication
■ √ means can be chosen, and - means can not. If you want no unexpected stop after starting or no unex-
pected starting during maintenance, then you can set the PD at 7, and it will forbid any starting or stop ope-
ration.
■ When it is allowed external control, please connect with a NC button switch or short circuit between the
external control terminals 08 and 10, so that when it is open circuit, it can not start the motor.
6-3 PJ is used to set the operating time of output relay
Value of PJ
When send
When
When
Operating time
the starting
starting
bypass
of output relay
order
running
■ When the P4 is not 0, then take the above time as starting point and begins time delay according to set
time of P4. When time delay finishes, it acts, when P4 is 0, it will act immediately.
■ The output reset time (namely contact break) that is after P4 set time finishing delay, then retain 1s; if
start motor again, it breaks off last programming automatically, while, starting the cause. It can program
the relay output function flexibly, shorten the external control logic circuit efficiently.
6-4 Instruction for code PU motor underload protect
PU<10,prohibit motor under-voltage protection function, underload protection current scope is the
motor rated current of 10%~90%,be determined by the tens digit at PU. Underload protect delay for the
range of 5 to 90seconds,by setting the PU setup times 10 to determine, when PU units digit is 0,the protect
action delay for 20 seconds.
This series soft starter protected mode set the default for the "senior" at PC, if the customers require to
drive light load (such as light bulbs) debugging, need to modify protected mode "primary" at PC,
otherwise soft starter alarm.
Current value
Percent
Percent
Percent
When
When
When
When
When the
stop
finished
instantaneous
there
auto restart
stopping
stop
is fault
is finished
-12-