Anderson 80G5300 Kullanım Kılavuzu - Sayfa 10

Brülör Anderson 80G5300 için çevrimiçi göz atın veya pdf Kullanım Kılavuzu indirin. Anderson 80G5300 17 sayfaları.

10.6 Checklist after installation

To verify the system was properly installed, perform the following checks:
– Be sure there are no leaks in the gas lines.
– Be sure all the components contained in the flame monitoring and control system,
pressure switch and wiring are properly installed.
– Be sure all components of the spark ignition system are installed and functioning
properly.
– Be sure the blower rotates in the proper direction. If the rotation is incorrect, have
a qualified electrician rewire the blower to rotate in the proper direction.
– Be sure all valves are installed in the proper location and correctly oriented relative
to the flow direction.

10.7 Prepare for adjustment

After installation of the burner system components is complete, the following steps
should be followed in order to prepare for adjustment:
– Set the air flow switch so that it drops out at 20% of the maximum pressure of the
combustion air blower.
– Set the low gas pressure switch at 50% below the gas pressure measured at the inlet
to the main gas valve train.
– Set the high gas pressure switch at 50% above the gas pressure measured at the
inlet to the main gas valve train.
– Try to ignite the burner before the purge and other timers have finished their cycles.
Make sure that the flame monitoring system indicates a flame failure.
– Trip out the pressure switches and other limit interlocks. Make sure that the main
gas valve train closes.
– If the simulated limit condition or the simulated flame fault cannot be responded at
the specified fault response time, the fuel system needs to be turned off to correct
the existing problems.

10.8 Burner commission

Special attention:
The SSA80 Series burners, described herein, are designed to mix fuel with air. All fuel
burning devices are capable of producing fires and explosions, if improperly applied,
installed, adjusted, controlled, or maintained. Do not bypass any safety feature; fire
or explosion could result. Never try to light a burner if it shows signs of damage or
malfunction.
If you are adjusting burner for the first time, you must follow these steps
1.
Reset the system: Start circulating duct fan with valve fully open, close all the
automatic gas valves and manual gas cocks. Pay more attention to rotate direction
of blower.
2.
Set the system to high fire, but DO NOT ignite the burner(s). Use the datasheet
Anderson Thermal Soluions(Suzhou)Co., Ltd
Anderson Thermal Solutions – SSA80 Operation Manual
8