– Visually check igniter cable and connectors.
– Be sure the burner bodies and air wings, the ignite and the flame sensors are not
damaged or distorted.
12. Troubleshooting Procedures
Problem
Cannot initiate a
start sequence
Start–up sequence
runs but
burner does not light
Anderson Thermal Soluions(Suzhou)Co. ,Ltd.
Anderson Thermal Solutions – ANM75 Burner Operation Manual
Possible Cause
Air pressure switch has not made
contact
High gas pressure switch has activated.
Low gas pressure switch has activated
Purge cycle not completed.
Malfunction of the flame safeguard
system (e.g., flame sensor failure or
electrical noise in the sensor line).
No power to the control unit.
Main power is off.
PILOT IGNITION ONLY
Pilot gas pressure low
Pilot gas cock closed
Pilot solenoid valve close
Gas adjusting valve set too low
Air in the pilot line
PILOT IGNITION OR DIRECT SPARK
Attempting to ignite at inputs greater
than 60%
Weak or non–existent spark.
Check air pressure switch adjustment.
Check air filter.
Check blower rotation.
Check outlet pressure from blower.
Check incoming gas pressure; adjust if
necessary.
Check pressure switch setting and
operation
Check flame safeguard system or
purge timer.
Have a qualified electrician
troubleshoot and correct the problem.
Be sure the main power to the system
is switched to the "on" position
Adjust pilot gas pressure
Open pilot gas cock
Check wire for solenoid valve
Increase opening of the valve
Repeat start for several times
Reduce start point gas flow.
Verify control circuit.
Verify ignition transformer is a 6,000 –
8,000 Volt transformer
10
Solution