Gas and oxygen must be equipped with check valves,
otherwise tempering may occur.
–
Ensure that the furnace temperature is above the minimum
requirement for the ignition temperature of the fuel.
4.3 Burner start
Before starting, verify that all shut-off valves for natural gas and oxygen are closed before
starting. Check that the gas and oxygen hoses are properly and securely connected to the
burner. Prepare the gas and oxygen lines, open the oxygen shutoff valve closest to the burner,
and let oxygen flow through the burner at a rate of about 30 standard cubic meters per hour
to cool the burner. Open the corresponding gas flow regulating valve to establish the gas
flow. Initially adjust the oxygen/gas ratio to 2: 1. The oxygen and gas flow can then be
adjusted according to normal actual parameters
Repeat the above steps until all burners are ignited.
4.4 Burner shut down
To temporarily close the burner, you need to close the front stop valve of the natural gas
burner. Then adjust the oxygen gas flow to a minimum cooling flow of 30Nm
does not need to be removed from the burner block at this time.
Do not use this burner if stopped for a long time. You need to close the ball valve burner
downcomer, and then close the oxygen ball valve on downcomer. Disconnect the oxygen and
natural gas quick connector and remove the burner from the bracket. Use insulation fiber to
block burner block opening.
4.5 Burner maintenance
The burner requires regular inspection. Inspection after long periods of non-use is
particularly important. During the first month of burner operation, the nozzles need to be
inspected weekly. In the second month, the frequency of inspections can be extended to
once every two weeks. Anderson recommends that each nozzle be inspected at least monthly.
At each inspection, the burner needs to be removed from the burner block in order to fully
check the status of the burner.
5. Spare parts
With proper use and regular servicing of the burner, we recommend the following parts:
–
Quick Coupler high temperature gasket
–
Outer nozzle gasket
–
Spare burner nozzle
Anderson Thermal Soluions(Suzhou)Co., Ltd