Anderson VFI84 Kullanım Kılavuzu - Sayfa 4

Brülör Anderson VFI84 için çevrimiçi göz atın veya pdf Kullanım Kılavuzu indirin. Anderson VFI84 15 sayfaları.

Anderson Thermal Solutions – VFI84 Burner Operation Manual
combustion chamber is purged. If it is ignited at a low temperature, it needs to be replaced
with 5 times the volume of the combustion chamber to avoid explosion.
However, it is not necessary to purge when the temperature is higher than 750°C. Air pipe
or gas pipe connected with burner should be tight enough with no leakage, also the
periodically check air or fuel nozzles of the burners to prevent to be blocked by dust, slag
or other materials.
ATTENTION:DANGER OF BEEN BURNT
When burner in operation, combustion is severe, so the burner must be fixed inposition.
Hoses or cables in area of the combustion system must be suitable for high temperature,
to prevent high temperature failure or cause safety accidents. Burners should be
periodically inspected and cleaned. Copper wire brush may be used, if necessary, to clean
burner head. The burner system should be checked twice a year for safety operation.
Burner commissioning shall take care of ignition position, minimum and maximum output
position. Following interlocks will cause emergency stop, including gas low pressure, high
pressure or low combustion air pressure, as well as emergency stop is trigged, the main
power is out, UV signal failure or kiln safety conditions (such as high temperature limit, flue
system opening, etc.) will cause the burner lockout. Users need to know the maintenance
interval recommended by the manufacturer and the interval specified by national laws,
whichever is shorter.

4. Fuel Information

Following table shows combustion fuel characters of natural gas and oxygen, safety rules
must be obeyed when operation carried out.
Fuel
Natural gas
Low Calorific value
35,900 [kJ/m3]
Composition
>98% CH4
Reference conditions
1,013.25 mbar, 0°C

5. VFI84 Series Burner Description

VFI84 series of burners are the patented products of Anderson Thermal Solutions (Suzhou)
Co., Ltd. Designed for the incineration exhaust from dryers, ovens and other similar
equipment. The burners are nozzle mixture type.
Anderson Thermal Soluions(Suzhou)Co., Ltd
2