Anderson LA Series Kullanım Kılavuzu - Sayfa 3

Verici Anderson LA Series için çevrimiçi göz atın veya pdf Kullanım Kılavuzu indirin. Anderson LA Series 18 sayfaları. Level transmitter

Section 1 General

1.1 INTRODUCTION

1.1 INTRODUCTION
1.1 INTRODUCTION
1.1 INTRODUCTION
1.1 INTRODUCTION
The Anderson "LD/LA" standard and pharmaceutical series level transmitters are unique
devices designed for level control applications where pressure based technology provides
the best overall solution, but where bottom access for the sensor is not available or prefer-
able. These sensors are designed to be mounted on the top of the vessel with the extension
tube positioning the sensing diaphragm near the bottom of the tank. Common applications
include rotary filler bowls, surge tanks and small processing storage vessels where bottom
access is impractical. With no moving parts, no air required, and wide compensated
temperature range the LD/LA provides accuracy and repeatability in applications where
other sensing technologies have been proven unreliable.

1.2 SPECIFICATIONS

1.2 SPECIFICATIONS
1.2 SPECIFICATIONS
1.2 SPECIFICATIONS
1.2 SPECIFICATIONS
Performance
Upper Range Limit (URL)
Minimum Span:
Over-Range Capacity:
Accuracy:
Repeatability:
Stability:
Compensated Temp. Range: 30°F to 220°F (-1°C to 104°C)
(process)
Compensated Temp. Range: 30°F to 120°F (-1°C to 49°C)
(ambient)
Effect of Process/Ambient
Temperature Change:
Humidity:
Response Time:
Power Signal
Output:
Loop Power required:
Effect of Voltage Change:
Load Impedance:
Cable Recommended:
Materials/Construction
Housing /Wiring Head:
Wetted Parts:
Surface Finish (LD):
Surface Finish (LA - Pharm.)
Housing Rating:
Agency Approvals
Electronic "Noise"
Immunity:
Sanitary Standards:
Hazardous Locations:
Warranty:
72" water column (w.c.)
30" w.c.
2.5 times the URL (180" w.c.)
± 0.75% of URL (± 0.5" w.c.)
within ±0.3% of URL (± 0.2" w.c.)
Within published specification for one
(1) year minimum
± 0.40% of URL per 10°F
0-100% RH, Condensing
526 mSec
4-20mA dc
12-40 Vdc
± 0.05% of URL per 30 volts
1550 Ohms at 40 VDC
18-24 AWG, .169" to .209" diameter,
stranded, 2 conductor with ground,
shielded and PVC coated for use with
seal-tight wire grommet
304 stainless steel
316L stainless steel
Ra=25 microinches or better (wettedparts)
Ra=15 microinches or better (wetted parts)
NEMA 4X, IP-65
Designed to meet IEC 801-2, -3 and -4,
Level 3, CE Compliant
Complies with all applicable provisions
of 3-A Sanitary Standards (74-00).
For LA only: UL, Intrinsically safe for use in CLass 1, Div. 1 Groups A-D.
All units are covered by a two (2) year warranty against defects in material
and workmanship when installed and maintained according to the instruction
manual provided.
P
3
AGE