Atkinson Electronics GSCM-MINI-50 Manuel - Sayfa 3
Kontrol Ünitesi Atkinson Electronics GSCM-MINI-50 için çevrimiçi göz atın veya pdf Manuel indirin. Atkinson Electronics GSCM-MINI-50 12 sayfaları. Generator start control module - mini (2 wire to 3 wire)
GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
OPTION #1 MOMENTARY START CONTACT - TYPICAL GENERATOR W/ STARTER CONTROL BOX
The K1 relay is used to switch the start/crank input which is looking for a momentary signal and opens when the generator has reached
50Hz, or half speed. The K2 relay provides a momentary "stop" signal until the generator AC Hz has dropped to zero. For GSCM-mini
operational sequence details see Page 4, Section - 1
OPTION #2 MAINTAINED START CONTACT TYPICAL GENERATOR W/ STARTER CONTROL BOX
The K1 relay provides a continuous run signal for generators
requiring a "maintained" start signal. The K2 relay provides a
momentary "stop" signal until the generator AC Hz has
dropped to zero. For GSCM-mini operational sequence details
see Page 4, Section - 2
OPTION #3 IGNITION KEY SWITCH TYPE START CONTACT TYPICAL GENERATOR W/ STARTER CONTROL
The K1 relay is used to switch the starter input which is
looking for a momentary signal and opens when the generator
has reached 35Hz. The K2 relay provides a continuous run
signal for generators requiring a "maintained" ignition signal.
When the GSCM-mini no longer receives a run command
signal (terminal 5 or batteries fully charged, K2 relay opens
telling the generator to shutdown. For GSCM-mini operational
sequence details see Page 5, Section - 3
ATKINSON ELECTRONICS, INC.
Web Site: www.atkinsonelectronics.com
A double pole "kill switch" wired and installed by the user, stops
the generator instantly in emergency situations such as a fuel
spill. One switch pole (N.C.) kills power to the GSCM-mini
opening all relays. The other switch pole (N.O.) shorts out the
magneto for an instant stop.
A single pole "kill switch" wired and installed by the user, stops
the generator instantly in emergency situations such as a fuel
spill. One switch pole (N.C.) kills power to the GSCM-mini
opening all relays shutting down the ignition switch type
generators.
Distributed by:
GSCM-MINI-50HZ
REV 5/08