3.4) Fuse and overload protection

Fuse ratings and type
Fuses F1 – F2
gG
Fuses F3 – F4
Amperage requirement
415V 3ph
Step 1 F3
(22x58)
Step2
(22x58)
ELECTRICAL CIRCUIT
 The Compacte electric boiler must be provided with 415volts and
without neutral wiring
 The electrical wiring cables must be sized by a qualified electrician in
order to conform
to BS C 15100 and satisfying load, length of run and prevention of short
circuit.
 The installation must be tested for automatic power failure in the
event of emergency
power cut, heater lock-out or error in the neutral layout.
 All electrical equipment shall satisfy IP21/IK08 Class 1
 The immersion heaters shall only receive electrical power if they are
fully immersed in water; otherwise the guarantee on the heaters will
not apply
ALL ELECTRICAL WIRING MUST BE CORRECTLY EARTHED
cartridge F1 – 1A type aM, cartridge F2 – 1A type
cartridge F3 & F4 type 10 x 38 to 22 x 58
36kW
40A (14x51) 40A (14x51) 63A (22x58) 63A
Km1
24kW
F4
20A (10x38) 40A (14x51) 40A (14x51) 63A
Km2
12kW
48kW
24kW
24kW
11
60kW
72kW
36kW
36kW
24kW
36kW