Connection of cables, strip leads and earthing
Notice: In the case of connecting the cable on the
fixed insulator side by means of cable eye, a Cu-Al
washer must be inserted between the cable eye and
the connecting lug (under the cable eye).
Strip leads are mounted on the device contacts
straight (in contact axis – see photo). This applies
also to the middle, symmetrical pole of the device.
The middle pole strips are provided with a skew fork
pull rod on the conductor side.
The marked earthing terminal on the disconnector
frame and the device drive is used for the earthing
of disconnector.
Permitted tension in conductors:
ATTENTION:
It is not allowed to use the load disconnector frame as a support for conductor tightening.
Permitted tilt of the conductors
one-side load: 5 kN/conductor
two-side load: 15 kN/conductor
7
Detail of connecting strip leads