Daikin AWS Kurulum ve Bakım Kılavuzu - Sayfa 4
Kontrolör Daikin AWS için çevrimiçi göz atın veya pdf Kurulum ve Bakım Kılavuzu indirin. Daikin AWS 14 sayfaları. Chiller unit controller/communication module
The L
W
communication module connects the
on
orks
MicroTech III chiller unit controller to a building automation
system (BAS). This interface enables the exchange of
L
W
variables between the unit controller and a
on
orks
L
W
Operating Network or LON.
on
orks
Features
• Integration into a building automation and control system
via L
W
on
orks
• LonMark
3.4 certified with conformance to the chiller
®
functional profile
• Network controller (Neuron chip) handles the complete
L
W
network protocol and user application
on
orks
• Simple attachment to a MicroTech III chiller unit controller
• LEDs that indicate communication status and network
activity
• Configurable using standard L
tools such as Echelon's
• Circuit board components enclosed in protective housing
Specifications
The following section provides a summary of technical data
and conformance to agency listings.
General
Dimensions
W × H × D: 1.77 × 4.33 × 2.95 in (45 × 110 × 75 mm)
Weight
3.0 oz (85 g)
Base - plastic, pigeon-blue
Material
Housing - plastic, light-gray
Operating
Temperature
-40 – 158°F (-40 – 70°C)
Humidity
<90% RH
Min. 10 psi (70kPa), corresponding to max. 9,842 ft
Atmospheric pressure
(3,000 m) above sea level
Storage and Transportation
Temperature
-40 – 158°F (-40 – 70°C)
Humidity
<95% RH
Min. 3.77 psi (26 kPa), corresponding to max.
Atmospheric pressure
32,808 ft (10,000 m) above sea level
Electrical
Supplied via unit controller
Power
DC 5 V (+5% / –5%), max. 80 mA
LON interface: Plug-in terminals 2 wires,
Network cable
interchangeable
Galvanically isolated, 78k baud TP/FT-10 transceiver
Bus connection/
Connection to Bus via the T1 port
Transceiver
Terminal plug: 2-pin spring cage top entry
L
W
data memory 56 kbyte flash memory for the user application
on
orks
Additional Components
Board-to-board
10-pin plug between communication module and unit
connector
controller
Agency Listings
US
UL916, UL873
Canada
CSA C22.2M205
Europe
EMC directive
2004/108/EC
Low-voltage directive
2006/95/EC
RoHS directive
2002/95/EC
IM 968-4 • MICROTECH III CHILLER UNIT CONTROLLER
W
commissioning
on
orks
LonMaker
software
®
®
Dimensions
Figure 1
and
Figure 2
provide key dimensional data.
Figure 1: L
W
Communication Module Top View
on
orks
Figure 2: L
W
Communication Module Side View
on
orks
4.33 in (110 mm)
4
I
nTroduCTIon
MT3043
1.77 in (45 mm)
1.77 in (45 mm)
4.57 in (116 mm)
www.DaikinApplied.com