2

About the box

2.1

Outdoor unit

2.1.1
To remove the accessories from the
outdoor unit
a
b
c
a
Outdoor unit installation manual
b
Multilingual fluorinated greenhouse gases label
c
Drain plug (located on the bottom of the packing case)
d
Energy label
e
Fluorinated greenhouse gases label
3

Unit installation

3.1

Preparing the installation site

WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
3.1.1
Installation site requirements of the
outdoor unit
Mind the following spacing guidelines:
b
>250
a
>250
b
>250
a
>250
(mm)
a
Air outlet
b
Air inlet
NOTICE
The height of the wall on the outlet side of the outdoor unit
MUST be ≤1200 mm.
It is recommended to install a baffle plate when the air outlet is
exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing
the wall and NOT directly exposed to the wind.
Do NOT install the unit in sound sensitive areas (e.g. near a
bedroom), so that the operation noise will cause no trouble.
ERLA03DAV3
Daikin Altherma 3 R
4P596797-1 – 2019.10
d
e
a
>350
b
>250
b
>250
a
a
>350
b
Note: If the sound is measured under actual installation conditions,
the measured value might be higher than the sound pressure level
mentioned in "Sound spectrum" in the data book due to
environmental noise and sound reflections.
INFORMATION
The sound pressure level is less than 70 dBA.
The outdoor unit is designed for outdoor installation only, and for the
following ambient temperatures:
Cooling mode
Heating mode
3.1.2
Additional installation site requirements
of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.
c
a
Snow cover or shed
b
Pedestal
c
Prevailing wind direction
d
Air outlet
It is recommended to provide at least 150  mm of free space below
the unit (300 mm for heavy snowfall areas). Additionally, make sure
the unit is positioned at least 100 mm above the maximum expected
level of snow. If necessary, construct a pedestal. See
unit" [ 4  6] for more details.
the outdoor
In heavy snowfall areas it is very important to select an installation
site where the snow will NOT affect the unit. If lateral snowfall is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.
By default, the outdoor unit heat pump can operate until –7°C.
Depending on the installation area, this can be lowered to –15°C by
modifying the BUH
only
ambient
setting. This setting can also be changed via the menu structure.
See the installation manual of the indoor unit for how to change the
setting.
Additionally, in areas with ambient temperatures between –7°C and
–15°C, and depending on the altitude of the unit, the installation of a
bottom plate heater (EKBPHT03D) may be required to guarantee
outdoor unit operation.
2 About the box
10~43°C
–15~25°C
a
c
b
"3.2 Mounting
temperature ([8-0E]) field
Installation manual
5