Daintree GE current 93013522 Kurulum Kılavuzu - Sayfa 4

Fener Daintree GE current 93013522 için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. Daintree GE current 93013522 4 sayfaları. Led luminaire

Lumination
(Tetra
®
Electrical Connections
1
Strip the ends of the wire 1/2-inch (13 mm) on the modules
(white and red) of adjacent columns that you want to connect.
2
Use UL approved wire connectors (twist-on or in-line connectors)
and 18 AWG (0.82 mm
) wire to connect the corresponding wires.
2
3
Strip the end of the wire 1/2-inch (13 mm) on the first column
of modules and connect to the output of the LED Driver. Output
connections must be red-to-red and white-to-black.
4
Refer to the LED Driver Installation Instructions for
more information on connecting the LED Driver.
Troubleshooting
Symptom
Row of modules does not light
All modules do not light
Individual modules do not light
Modules are dim
Loading Chart
LED Driver
79045 (GE080/MV/D24T1-A)
67825 (GEPS24-100UGL-IP)
62189 (GE180/MV/V24T1-C)
Remote Mounting Distance
LED Driver
79045 (GE080/MV/D24T1-A)
67825 (GEPS24-100UGL-IP)
62189 (GE180/MV/V24T1-C)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference,
and (2) this device must accept any interference received, including interference that may cause undesired operation. This Class [A] RFLD complies with the
Canadian standard ICES-003. Ce DEFR de la classe [ A ] est conforme á la NMB-003 du Canada.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference
to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required
to correct the interference at his own expense.
PowerGrid - Series)
®
• Check wire connections to LED Driver to ensure red-to-red and white-to-white connections.
• Check row-to-row polarity connections.
• Check input voltage and check LED Driver input/output connections.
• Check wire connection attachment and polarity of wires.
• Ensure the overall length of modules does not exceed the maximum load for the LED Driver.
• Ensure the length of the supply wire is equal to or below the recommended remote mounting distance
(see remote mounting distance chart above).
Minimum Loading
1 Module
1 Module
1 Module
18 AWG (0.82mm
Supply Wire
1-30 ft. (0.3-9.1m)
www.gecurrent.com
© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the
General Electric Company and are used under license. Information provided is subject to change without
notice. All values are design or typical values when measured under laboratory conditions.
ARCH015 (Rev 04/02/2021)
LED Driver
Solution
33 Modules/22 ft. (6.7m) per Bank; 66 Modules/44 ft. (13.4m) per Driver
)
16 AWG (1.31mm
)
14 AWG (2.08mm
2
2
Supply Wire
1-50 ft. (0.3-15.2m)
Installation Guide
Wire connections
Cap all unused wires
Maximum Loading
30 Modules/20 ft. (6.1m)
36 Modules/24 ft. (7.3m)
)
12 AWG (3.31mm
2
Supply Wire
Supply Wire
1-80 ft. (0.3-24.4m)
1-120 ft. (0.3-36.6m)
)
2