6
Troubleshooting
No LEDs turn on when I press the Utility button.
Check battery installation.
Make sure batteries are oriented (+ -) correctly.
The red Infrared Detection LED does not activate when walking
through the coverage area while in Installation Test mode.
Check to see if the red LED turns on when you wave your
hand directly in front of the lens.
– If the red LED turns on, adjust the PIR Sensitivity trimpot
clockwise to increase sensitivity. Check for objects or
barriers obstructing the sensor's view of the coverage area.
– If the red LED does not turn on, the Installation Test mode
may have timed out. Restart the Installation Test mode by
momentarily pressing the Utility button. The green LED
turns on briefly, then the red LED flashes with each
detection. Installation Test mode times out in 5 minutes.
The red LED flashes when nobody is moving in the
coverage area.
Adjust the PIR sensitivity trimpot counter-clockwise to
reduce sensitivity. Repeat the walk test.
Check for sources of hot airflow in the coverage area.
Review the Placement guidelines and eliminate false
trigger sources.
If lights do not turn Off after the WOS2-CM has Joined the
ZigBee network:
Check the "Off delay" for the zone in the Daintree
Controls Software.
Check for other DCS scheduled events or manual overrides
that may be keeping the lights On.
7
FCC Warning Message
This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment
generates, uses and radiates radio frequency energy and, if not
installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning
the equipment off and on, the user is encourage to try to correct
the interference by one or more of the following measures:
Reorient or relocate the receiving antenna;
Increase the separation between the equipment and receiver;
Connect the equipment into an outlet on a circuit different
from that to which the receiver is connected;
Consult the dealer or an experienced radio/TV technician
for help.
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation
or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be
referred to GE Current, a Daintree company.
8
Industry Canada (IC) Warning Message
Product complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) This device must accept any
interference received, including interference that may cause
undesired operation.
Power Supply
Battery Life
Radio Properties
Sensor Coverage
(maximum)
Off-Delay Timer
Operating
Environment
Compliance
Mounting
Dimensions
WOS2-WM
CAUTION
RISK OF EXPOSURE IF BATTERY IS REPLACED BY AN
INCORRECT TYPE. DISPOSAL OF USED BATTERIES
ACCORDING TO THE INSTRUCTIONS.
Questions:
Web: products.gecurrent.com
Phone: 1-866-855-8629
www.gecurrent.com
© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the
General Electric Company and are used under license. Information provided is subject to change without notice.
All values are design or typical values when measured under laboratory conditions.
DT106 (Rev. 03/30/2021
Installation Guide
Specifications
2) Lithium-thionyl chloride batteries
(Li-SOCl2) AA 3.6V (included)
5 years (normal operation)
2.4 GHz, +7dBm transmit power
110°, 11 m/36 (WOS2-WM-W)
20°, 30 m/98 (WOS2-WM-L)
14° to 122° F (-10° to 50° C)
14°F to +122°F (-10°C to 5 0°C)
Indoor use only
FCC Part 15 B, FCC ID: NRH-ZB-Z100B
ICES/NMB-003 Class B, IC: 8984A-Z100B
(2) Screw holes on base plate;
ceiling mount; twist-lock sensor
3.6" W x 2.8" H x 3" D
(92mm W x 70mm H x 77mm D) Weight