Wireless Occupancy Sensor, Recess Mount (WOS2-RM)
®
4
Sensor Placement (continued)
5
Joining the ZigBee Network
After successfully completing the Installation Test the
occupancy sensor is ready to communicate with the
Daintree Wireless Area Controller (WAC).
* A network join can be retriggered manually at any
time using one of the following methods:
• Reset to factory defaults: This causes the device to
leave any network to which it is currently joined.
Following the reset, the device attempts to join a
network. Press and hold the Utility button for
5 seconds. Release the button when the Network
LED begins to flash rapidly.
• Activate device: Press and hold the Utility button
for 2 seconds. If the device is already joined to a
network, the Network LED flashes twice. If the
device is not joined to a network, the Network
LED flashes rapidly and the device will attempt
to join a network.
For more information about configuring the lighting
control network, see the instructions and on-line help
provided with the Daintree Controls Software (DCS)
web application.
6
Troubleshooting
No LEDs turn on when I press the Utility button.
Check battery installation.
•
Make sure batteries are oriented (+ -) correctly.
•
The red Infrared Detection LED does not activate when walking
through the coverage area while in Installation Test mode.
• Make sure that the lens is not obstructed and there is no
debris on the lens.
• Check to see if the red LED turns on when you
wave your hand directly in front of the lens.
– If the red LED turns on, adjust the PIR Sensitivity trimpot
clockwise to increase sensitivity. Check for objects or barriers
obstructing the sensor's view of the coverage area.
– If the red LED does not turn on, the Installation Test mode
may have timed out. Restart the Installation Test mode by
momentarily pressing the Utility button. The green LED turns
on, then the red LED flashes with each detection. Installation
Test mode times out in 5 minutes.
The red LED flashes when nobody is moving in the
coverage area.
•
Adjust the PIR sensitivity trimpot counter-clockwise to
reduce sensitivity. Repeat the walk test.
Check for sources of hot airflow in the coverage area.
•
Review the Placement guidelines and eliminate false
•
trigger sources.
If lights do not turn Off after the WOS2-CM has Joined the
ZigBee network:
Check the "Off delay" for the zone in the Daintree
•
Controls Software.
Check for other DCS scheduled events or manual overrides
•
that may be keeping the lights On.
4