Operating and recommended Routine Test Procedure
Follow these instructions carefully to ensure safe and reliable operation of this emergency luminaire. The following testing is designed to ensure the
continued protection of your premises and occupants, in the event of the possibility of a failure of the normal lighting supply.
Testing should be carried out in accordance with the recommendations of BS5266.
A daily check – check LED charge indicator is illuminated
A monthly functional test – simulate a mains supply failure for approx. 30 seconds by operation of key switch or switching off circuit
breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated.
Twice yearly, a one hour duration test - simulate a mains supply failure for a one hour continuous test by operation of key switch or
switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated.
Every three years, a full three hour duration test - simulate a mains supply failure for a three hour continuous test by operation of key
switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated.
To assist with this testing, a test record is included. If the luminaire fails any of the above tests, please contact a qualified electrician.
TEST RECORD SHEET
F IR S T Y E A R
TE S T
M O N T H
S ig ne d
1
F U N C TIO N A L
2
F U N C TIO N A L
3
F U N C TIO N A L
4
F U N C TIO N A L
5
F U N C TIO N A L
6
1 H O U R
7
F U N C TIO N A L
8
F U N C TIO N A L
9
F U N C TIO N A L
1 0
F U N C TIO N A L
1 1
F U N C TIO N A L
1 2
3 H O U R
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Maintenance:
1. Where applicable, it is important to ensure failed lamps are replaced immediately in order to prevent damage to the control gear.
2. Always replace lamps with the same lamp type and wattage as supplied. When replacing Metal Halide Lamps it is important to
note that there are different types of Metal Halide Lamps and some types of lamps will not be suitable for use with the control gear
fitted within this luminaire. If you are in doubt, please contact your equipment supplier or Ansell Lighting for further advice.
Disposal of Electronic Equipment WEEE Directive 2002/96/EC
This product falls within the scope of the Waste Electrical & Electronic Equipment Directive
(WEEE), which means the product should not be disposed of as normal household waste.
Ensure that this luminaire and lamp is disposed of in accordance with the WEEE Directive.
Contact a local Council Waste Dept. Local Amenity Site, or the DTI for further information.
RoHS - All components and materials used in this product are RoHS 2002/95/EC compliant.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Page No. 2
®