DSE 7420 Kurulum Talimatları - Sayfa 2

Kontrolör DSE 7420 için çevrimiçi göz atın veya pdf Kurulum Talimatları indirin. DSE 7420 2 sayfaları.

ADJUSTABLE PARAMETERS
Front Panel Configuration Editor
Section
Parameter as shown on display
Display
Contrast
Language
Current Date and Time
Timers
LCD Page Timer
Scroll Delay
Engine Pre Heat Timer
Engine Crank Duration
Engine Crank Rest Time
Engine Safety On Delay
Engine Smoke Limiting
Engine Smoke Limiting Off
Engine Warm Up Time
Engine Cool Down Time
Engine Speed Overshoot Delay
Engine Failed To Stop
Battery Under Voltage Warning Delay
Battery Over Voltage Warning Delay
Return Delay
Generator Transient Delay
Mains Transient Delay
Mains transfer time
Mains
Mains Under Voltage Alarm
Mains Over Voltage Alarm
Mains Under Frequency Alarm
Mains over Frequency Alarm
Mains Transient Delay
CT Primary
CT Secondary
Mains kW Rating
Mains kVar Rating
Under Voltage Shutdown
Generator
Under Voltage Pre-Alarm
Nominal Voltage
Over Voltage Pre-Alarm
Over Voltage Shutdown
Under Frequency Shutdown
Under Frequency Pre-Alarm
Nominal frequency
Over Frequency Pre-Alarm
Over Frequency Shutdown
Full Load Rating
kW Overload Trip
Delayed Over current
Delayed Over Current
AC System
CT Primary
CT Secondary
Short Circuit Trip
Earth CT Primary
Earth Fault Trip
Earth Fault Trip
Transient Delay
Gen Reverse Power Delay
Gen Reverse Power
Engine
Oil Pressure Low shutdown
Oil Pressure Low Pre-Alarm
Coolant Temp High Pre-Alarm
Coolant Temp High Electrical Trip
Coolant Temp High Shutdown
Start Delay Off load
Start Delay on load
Start Delay Telemetry
Pre Heat Timer
Crank Duration
Crank rest Time
Safety On Delay
Smoke Limiting
Smoke limiting off
Warm Up Time
Cool Down Time
Speed Overshoot Delay
Speed Overshoot
Fail To Stop Delay
Battery Under Volts Warning
Battery Under Volts Warning Delay
Battery Under Volts Warning
Battery Over Volts Warning
Battery Over Volts Warning Delay
Battery Over Volts Warning
Charge Alternator Failure Warning
Continued Overleaf
Values
53%
English, others.
hh:mm
5m
2s
0s
10s
10s
10s
0s
0s
0s
1m
0s
30s
1m
1m
30s
0s
2s
0.7s
184v
277v
45Hz
55Hz
2s
600A
5A
345kW
258kW
184v
196v
230v
265v
277v
40Hz
42Hz
50Hz
54Hz
57Hz
500A
100%
Active
100%
3 Phase 4 Wire
600A
Power Cycle After Exit
5A
Power Cycle After Exit
200%
500A
Active
10%
0s
2s
35kW
1.03bar
1.24bar
90ºC
92ºC
(When Enabled)
95ºC
5s
5s
5s
0s
10s
10s
10s
0s
0s
0s
1m
0s
0%
30s
Active
1m
10v
Active
1m
30v
Active
Front Panel Configuration Editor (continued)
Section
Parameter as shown on display
Charge Alternator Failure Warning
Engine (continued)
Charge Alternator Warning Delay
Charge Alternator Failure Shutdown
Charge Alternator Failure Shutdown
Charge Alternator Shutdown Delay
Droop %
Scheduler
Scheduler
Schedule On Load
Schedule Period
Schedule Time & Date Selection
ACCESSING THE 'RUNNING' CONFIGURATION EDITOR
The 'running' editor can be entered while the engine is running. All protections remain active if the
engine is running while the running editor is entered.
Press and hold the
button to enter the running editor.
ADJUSTABLE PARAMETERS (Running editor)
Enter the editor as described above.
Press the up
or down
To Edit the parameter press the
button to enter edit mode. The parameter begins to flash to
indicate that you are editing the value.
Press the up
or down
Press the
button to save the value. The parameter ceases flashing to indicate that it has been
saved.
To exit the editor at any time , press and hold the
Running Editor
Section
Parameter as shown on display
DISPLAY
Contrast
Language
Values
6.0v
5s
Inactive
4.0v
5s
Active, Inactive.
droop is enabled.
Active, Inactive
Active , Inactive (Only Available When
Scheduler Is Active)
Weekly, Monthly (Only Available When
Scheduler Is Active)
Press
to begin editing then
(1-16)
when selecting the different
parameters in the scheduler.
buttons to cycle to the section you wish to view/change.
buttons to change the parameter to the required value.
button.
Factory Settings
53%
English
(When Enabled)
(When Enabled)
Electronic engines only when
or