Absolute Process Instruments API 1420 G Hızlı Başlangıç Kılavuzu

Endüstriyel Ekipmanlar Absolute Process Instruments API 1420 G için çevrimiçi göz atın veya pdf Hızlı Başlangıç Kılavuzu indirin. Absolute Process Instruments API 1420 G 2 sayfaları.

RTD Input Alarm Trips, Factory Ranged
Input:
2 or 3 Wire RTD
Output:
One 8 Amp DPDT Relay or Two 8 Amp SPDT Relays
O Automatic Leadwire Compensation
O Field Adjustable Setpoints
O Plug-In Design for Fast Installation
O Input LoopTracker
and Alarm Status LEDs
®
O Alarm Test Button
Applications
Q Process Limit Backup Alarm
Q Temperature Alarm
Q Over, Under, Out-of-Range Alarm
Temperature Input
Factory configured, please specify the following
Resistance at 0°C, curve, temperature range
10 Ω to 2000 Ω including 100 Ω 0.00385
RTD types:
DIN, 100 Ω 0.003916, 100 Ω 0.00392,
10 Ω Cu, 1000 Ω Ni-Fe, 120 Ω Ni
Temp. range:
°F or °C
100°F (55°C) min. span or consult factory
Leadwire Compensation
< ±0.05% of span per 1 Ω change in leadwire resistance
Excitation Current
10 Ω:
100 Ω:
10 mA
5 mA
1000 Ω: 0.5 mA
2000 Ω: 0.2 mA
LoopTracker
Variable brightness LED indicates input level and status
API 1400 G Relay Output
Two SPDT form C contact sets operating in unison as one
DPDT contact set
One setpoint, 12 turn potentiometer, 0-100% of span
Factory configured alarm type
Normal acting alarm
Standard: HI alarm
Optional: LO alarm
API 1420 G Relay Output
Two independent SPDT form C contact sets
Two setpoints, two 12 turn potentiometers, 0-100% of span
Normal acting alarms
Standard: HI/LO alarm
Options: LO/LO, HI/HI, LO/HI alarms
Internal jumpers for HI/LO, LO/LO, HI/HI, LO/HI
Relay Contact Rating
8 A @ 240 VAC resistive load or 30 VDC resistive load
See graph on other side for relay load ratings
Caution: Do not exceed socket voltage rating
Use an RC snubber for inductive loads
Deadband
Alarm trip/reset window is symmetrical about the setpoint
API 1400 G
1.0 to 100% of span, 12 turn potentiometer.
API 1420 G
Fixed at 1% of span, standard
API 1420 G A Adjustable deadbands, 1.0 to 100% of span,
1 turn potentiometer for each setpoint
Output Test Button
Toggles relay(s) to opposite state when pressed
Response Time
70 milliseconds typical
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than ±0.04% of span per °C stability, calculated, not
tested
Housing and Sockets
IP 40, requires installation in panel or enclosure
API 011 or API 011 FS socket
Socket mounts to 35 mm DIN rail or can be surface mounted
Power
Standard:
115 VAC ±10%, 50/60 Hz, 2.5 W max.
P option:
85-265 VAC 50/60 Hz, 60-300 VDC, 2.5 W typ.
A230 option: 230 VAC ±10%, 50/60 Hz, 2.5 W max.
D option:
9-30 VDC, 2.5 W typical
A
A
P
P
BSOLUTE
BSOLUTE
ROCESS
ROCESS
Variable Brightness Input LED
Bi-Color Relay LED
Deadband Adjustment
Setpoint Adjustment
Output Test Button
API 1400 G
A Option Deadband Adjustments
Variable Brightness Input LED
Bi-Color Relay 2 LED
Bi-Color Relay 1 LED
Setpoint 2 Adjustment
Setpoint 1 Adjustment
Output Test Button
API 1420 G
Description
The API 1400 G and API 1420 G are factory configured for an
RTD input and provide alarm contact outputs. Heavy duty relay
contacts allow the module to directly control high capacity
loads.
The API 1400 G provides a single setpoint adjustment and
DPDT relay contacts. The normal acting alarm output can
be factory configured for HI or LO operation. Top-accessible
potentiometers are used to adjust the alarm setpoint and
deadband.
The API 1420 G contains two independent setpoints with
two SPDT relay contact outputs. The normal acting alarm
output can be factory configured for HI/HI, HI/LO, LO/HI or
LO/LO operation. Top-accessible potentiometers are used to
adjust each alarm setpoint. Deadband is fixed at 1% of span.
Adjustable deadbands are optional.
Model
Input
API 1400 G
Factory ranged, specify
API 1400 G A230
RTD type,
RTD curve,
API 1400 G P
temperature range in °F or °C
API 1400 G D
API 1420 G
Factory ranged, specify
API 1420 G A230
RTD type,
RTD curve,
API 1420 G P
temperature range in °F or °C
API 1420 G D
Options—add to end of model number
L
1400 G with LO trip. Alarm trips on decreasing signal.
HH 1420 G with HI/HI trip. Alarms trip at their respective
trip points on increasing signal.
LL
1420 G with LO/LO trip. Alarms trip at their respective
trip points on decreasing signal.
LH 1420 G with LO/HI trip instead of HI/LO.
A
1420 G with adjustable deadbands.
U
Conformal coating for moisture resistance
I
I
NSTRUMENTS
NSTRUMENTS
API 1400 G, API 1420 G
2.38"
1.75"
2.38"
api-usa.com/1400
1.75"
LoopTracker and Alarm Status LEDs
API exclusive features include a LoopTracker LED that varies in
intensity with changes in the RTD input signal.
A red/green bi-color alarm status LED (two on the API 1420
G) visually indicate alarm status. These LEDs provide a quick
visual picture of your process at all times.
Output Test
API's exclusive functional test button can be used to verify the
alarm and system operation. Press the Test button to toggle
the alarm relay(s) to the opposite state. The output test but-
ton greatly aids in saving time during initial startup and/or
troubleshooting.
Standard Alarm Configuration
Single setpoint one DPDT relay
HI alarm, normal acting
2 setpoints, 2 SPDT relays
HI/LO alarms, normal acting
Accessories—order as a separate line item
API 011
API 011 FS 11-pin finger safe socket, DIN rail or surface mount
API CLP1
API 011 FS
300 V Rating
1220 American Way Libertyville, IL 60048
Phone:
800-942-0315
Fax: 800-949-7502
2.75"
Hot Swappable
Plug-In Design
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
Free Factory
Quick Link
I/O Setup!
Power
115 VAC
230 VAC
85-265 VAC or 60-300 VDC
9-30 VDC
115 VAC
230 VAC
85-265 VAC or 60-300 VDC
9-30 VDC
11-pin socket, DIN rail or surface mount
Module hold-down spring for high vibration or
mobile applications
API 011
API CLP1
300 V Rating
api-usa.com
©
09-21