Configuration Menu
Item
HP
HVAC
Parameters
√
√
1
Time format
√
√
2
Early Start
Automatic daylight
√
√
3
savings adjustment
√
√
4
Temperature format
√
5
Balance point low
√
6
Balance point high
√
7
Defrost point
√
8
Installation type
Auxiliary
√
9
interstage delay
√
10
Low temperature limit
√
11
High temperature limit
√
√
12
Cycles per hour
√
13
Heat type
√
14
Fan limit
√
√
15
Smart Fan
√
√
16
Temperature setback
Humidifier
√
√
17
operating mode
√
√
18
Dehumidifier type
Minimum air
√
√
19
exchange time
Note: Only items 1 to 4 are available when the controller is placed in user mode (SW1-1 switch).
TH146-P-U
Display
Options
Default
12 Hr / 24 Hr
24 Hr
On / OF
OF
OF / 1 / 2
OF
°C / °F
°C
-30 to 10°C
-10°C
(-22 to 50°F)
(14°F)
-5 to 30°C
5°C
(23 to 86°F)
(41°F)
-10 to 15°C
10°C
(14 to 59°F)
(50°F)
Ad / nr
Ad
5 to 90 min.
30 min.
-10 to 20°C
5°C
(14 to 68°F)
(41°F)
30 to 90°C
70°C
(86 to 194°F)
(158°F)
2 to 6
4
GA / EL
EL
38 to 90°C
80°C
(100 to 194°F)
(176°F)
On / OF
OF
0 to 9°C
0°C
(0 to 16°F)
(0°F)
Co / HE / Fn
Fn
Co / AE / dr
Co
0 - 60 min.
0
Description
Select the time display format.
•
On: Heating or cooling starts in advance (as determined by the control-
ler) so that the desired temperature is attained at the set times.
•
OF (Off): Heating or cooling starts at the set times.
NOTE: Early Start applies for periods 1 and 3 (P1 and P3) only. When this
feature is enabled, heating or cooling will start in advance of the set time for
P1 and P3 but will start at the set time for P2 and P4.
•
OF (Off): The function is deactivated.
•
1 : The controller switches to daylight savings time on the first Sunday of
April and to normal time on the last Sunday of October.
•
2 : The controller switches to daylight savings time on the second Sun-
day of March and to normal time on the first Sunday of November.
Select the temperature display format.
Set the bP L limit (see section 4.2).
NOTE: Lower bP L below its minimum (- -) if you do not wish to use this
function.
Set the bP H limit (see section 4.2).
NOTE: Raise bP H above its maximum (- -) if you do not wish to use this
function.
Set the defrost point temperature (see section 4.3).
NOTE: Raise the defrost point above its maximum (- -) if you do not wish to
use this function.
Set according to the type of heat pump installation (see section 4.4).
•
Ad (add-on): Use this setting when the indoor coils are located down-
stream of the auxiliary heat source. This is generally the case for add-on
installations.
•
nr (normal): Select this setting when the indoor coils are located
upstream of the auxiliary heat source. This is generally the case for new
installations.
Set the interstage delay for the auxiliary stage (see section 4.5).
Set the low temperature limit of the plenum (see section 4.6).
NOTE: This function is not used if you lower LLMT below its minimum
(- -) or if the plenum temperature sensor is not connected to the controller.
Set the high temperature limit of the plenum (see section 4.6).
NOTE: This function is not used if you raise HLMT above its maximum (- -)
or if the plenum temperature sensor is not connected to the controller.
Select the number of heating/cooling cycles per hour. For optimal heating
control, use the setting that matches your system as follows: 3=20 min (hot
water, 90%+ high-efficiency furnace), 4=15 min (gas or oil), 5=12 min (gas
or oil), 6=10 min (electric).
This setting determines the fan operation in automatic mode when the sys-
tem is in heating mode (see section 5.3).
•
EL (electric heating): The fan starts and stops at the same time as heat-
ing.
•
GA (gas or oil heating): The fan starts when the temperature inside the
plenum rises above the Fan Limit (see item 14) and stops when the tem-
perature drops 12°C below the Fan Limit. NOTE: The fan will not start if
the plenum temperature sensor is not connected to the controller.
This parameter is available only when gas heating is selected (see item 13).
WARNING: FLMT can be used in parallel with an UL353-approved device
but they do not replace such device.
NOTE: The fan will not start if you raise FLMT above its maximum (--).
•
On: Smart Fan is On (see section 4.7).
•
OF: Smart Fan is Off.
Set the amount of temperature setback when the controller is placed in
Unoccupied mode (see section 6.4).
•
Co (conventional): The humidifier will operate if the humidity is too low. If
the fan is not already On, it will turn On at the same time as the humidi-
fier.
•
HE (heat): The humidifier can operate only when heating is activated.
•
Fn (fan): The humidifier can operate as long as the fan is running,
whether heating is activated or not.
NOTE: The humidifier is disabled when cooling is activated.
Set according to the type of dehumidifier used.
•
Co (conventional): Select this setting when using a dehumidifier (except
an air exchanger) or when you do not wish to dehumidify.
•
AE (air exchanger): Select this setting when using an air exchanger (see
section 4.10).
•
dr (droop): Select this setting to dehumidify by droop (see section 4.9).
This parameter is available only if the controller is configured for using an
air exchanger (see item 18). Use it to set the minimum air exchange time
(see section 8.3).