Auber WS-1500EBPM Çalıştırma Talimat Kılavuzu - Sayfa 12

Sıcaklık Kontrolörü Auber WS-1500EBPM için çevrimiçi göz atın veya pdf Çalıştırma Talimat Kılavuzu indirin. Auber WS-1500EBPM 19 sayfaları. Ws series precision pid temperature controller

every 10 seconds. This parameter should set at 2 second for heating with an
electric heater. When controlling a solenoid valve or a compressor of refrigerator,
the T should be set to 10-20 to reduce the frequency of on/off.
To prevent changing critical parameters by accident, an access lock, LCK is used.
Special code is needed to open the lock for these parameters.
This group of parameters can be accessed by input code 166. Figure 8 is the flow chart
that shows how they can be changed.
Press and hold SET key for 4 seconds until LED displays "LCK." Then release the SET
key. The display will show "0". To get into parameters setting mode, you need to key in
the pass code. Use "+" and "-" keys to adjust the display to 166 (which is the pass code)
and press SET. The LED will show "P" for a second and then its P setting value, Use "+"
and "-" keys to change the setting. When finished, press the SET again to confirm the
change. The display will show the "I" for a second and its I setting value next, use the
same "P" setting procedure to set the I value. When finished, press the SET again to
confirm the change. The display will show the "d" for a second and its value next. Use the
same "P" setting procedure to set the d value. When finished, press the SET again to
confirm the change. The next setting is A, the auto-tune. Use "+" to set the value to 1
Figure 8. Code 166 Parameter setup flow chart
12