[Speci cations]
■General Speci cations
Ambient temperature/humidity for use
Ambient temperature/humidity for storage
Atmosphere for use
Altitude of use *
1
Pollution level *
2
Resistance to noise
*1 Do not use or store the AnyWireASLINK device in an environment pressurized equal to
or higher than the atmospheric pressure at the altitude of 0m. Doing so could cause a
malfunction.
*2 Index that indicates the occurrence of conductive material in the environment where the
device is used.
Contamination level 2 indicates that only non-conductive contamination occurs.
However, incidental condensation could create temporary conductivity in this
environment.
■Transmission speci cations
Power supply
Voltage 24V DC +15% to -10% (21.6 to 27.6V DC)
voltage for use
Ripple of 0.5Vp-p max.
Transmission method
DC power supply superimposed total frame/cyclic method
Synchronization method
Frame/bit synchronization method
Transmission procedure
Dedicated protocol
Connection mode
Bus type (Multi-drop method, T-branch method, Tree branch method)
Number of connection points
512 max. (IN: 256, OUT: 256)
Number of units connected
Up to 128 units
RAS feature
Transmission line disconnection, transmission line
short-circuit, transmission power supply reduction
detection ID redundancy, ID not set
■Individual speci cations
LA-A1AW: Input 16 points (Base unit)
Number of
occupied points
LB-A1AW: Input 16 points (Extension unit)
Number of
When connecting only LA-A1AW and LB-A1AW
connection
(LA-A1AW: n devices)+(LB-A1AW: m devices)≦16 devices
devices
20 mA (DP-DN) (Base unit)
Consumption
current
20 mA (DP-DN) (Extension unit)
Number of
1CH (Base unit)
analog input CH
1CH (Extension unit)
Measurement voltage range
0 - 10V, 0 - 5V, 1 - 5V (Input impedance 100k or more)
Measurement current range
0 - 20 mA, 4 - 20 mA (Input impedance within 250 ±5%)
±0.1% (16digit)
(25℃)
Accuracy
±0.2% (32digit)
(0~55℃)
Input
Input range
characteristics/
0-10V
Resolution
0-5V
1-5V
0-20mA
4-20mA
Input abnormality
Analog port open, disconnection: Digital value -200, ALM Display OFF
Input value over
Over the lower limit: Digital value -200, ALM display ON, Lo _ _ display
Over the upper limit: Digital value 16200, ALM display ON, hi
External supply
When connecting the power supply unit (LB-S24) to
current
each analog input unit Available supply: Between
24V-0V, MAX 100 mA/CH
12V, 30 mA
Absolute MAX input
5ms
Response time *
3
Mass
22 g (Base unit)
17 g (Extension)
*3 Time from detection of ON or OFF to sending of transmission signal.
This time plus the transmission 2 cycle time are transmission delay time.
0 - 55°C, 10 - 90%RH (No condensation)
-25 - 75°C, 10 - 90%RH (No condensation)
No corrosive gas
0 to 2000m
2 or less
1200Vp-p
Digital input value
Resolution
0-16000
625uV
0-16000
312.5uV
0-16000
250uV
0-16000
1250nA
0-16000
1000nA
[Outside Dimensions]
■LA-A1AW
■Transmission line
Φ1.1
■LB-A1AW
_ _
display
-L*A1AW 11/12-
(Base unit)
36.7
Transmission line
32
Φ4.1
Four cores, AWG24
Cable length: 200mm
(Extension unit)
36.7
32
* The length of LB-S24 is also the same.
Unit: mm