■Alarm value Hi setting
Set an upper limit for the alarm judgment value.
- Address writer (ARW-04, ARW-03): Parameter 03
Variable
Unit
0 - 100
%
Default: 80
* Set the alarm values so that Hi is greater than Lo.
■Alarm value Lo setting
Set a lower limit for the alarm judgment value.
- Address writer (ARW-04, ARW-03): Parameter 04
Default: BS-K4117-M12-1K : 19
Variable
Unit
BS-K4117-M18-1K : 25
BS-K4117-M30-1K : 27
0 - 100
%
* Set the alarm values so that Hi is greater than Lo.
■Alarm value monitor time setting
Set a monitor time for the alarm judgment value.
- Address writer (ARW-04, ARW-03): Parameter 05
Variable
Unit
3 - 255
100ms
Default: 50
■Normally open/Normally close setting
Set the normally open/normally close.
- Address writer (ARW-04, ARW-03): Parameter 06
Variable
Details
0
Normally open
ON with work present
1
Normally close
ON with work absent
■Setting for operation mode change
Set if there is an alarm diagnosis function.
- Address writer (ARW-04, ARW-03): Parameter 07
Variable
Details
0
Simple mode
Alarm diagnosis function disabled
1
Normal mode
Alarm diagnosis function enabled
■Setting for delay timer ON/OFF
Set the ON delay timer/OFF delay timer.
- Address writer (ARW-04, ARW-03): Parameter 10
Variable
0
No delay timer
Delay timer disabled
1
ON delay timer
ON delay timer enabled
2
OFF delay timer
OFF delay timer enabled
3
ON/OFF delay timer
ON/OFF delay timer enabled
■Setting for delay timer value
If you set the delay timer in parameter 10, you can set the delay time.
- Address writer (ARW-04, ARW-03): Parameter 11
Variable
Unit
10ms
0 - 255
Default: 0
Parameters [08, 09, 12 to 19] are items related to
CAUTION
internal settings. Do not perform settings.
Default: 0
Default: 0
Details
Default: 0
[Monitor display]
Displays the operation status of this product using the LEDs.
Normal state: LINK flashing, ALM off, IN ON on/OFF off
Name
LINK
(Green)
ALM
(Red)
LINK
ALM
IN
(Orange)
-BSK4117M**1K 7/9-
Indication status
On
Transmission signal error
Flashing
Transmission signal is appropriately supplied
Off
No transmission signal
On
Sensing level drop*
Flashing
Slave unit voltage drop
(On for 0.2 seconds,
off for 1.0 second)
Flashing
Teaching abnormality
(0.1 seconds alternately)
Off
Normal
Alternate flashing
When the master unit found that
LINK
the ID (address) of this unit is duplicate
or is not set.
ALM
On
ON
Off
OFF
* Only when alarm diagnosis function is enabled
ALM (Red)
IN (Orange)
LINK (Green)
Details