Internal Jumper Settings

This can be adjusted to increase the duration of the top-up cycle, and should be set by 3P in advance,
or otherwise adjusted by a qualified electrician or instrumentation technician.
The power supply MUST be disconnected before opening the Control Unit, there are hazardous
voltages inside.
Attention! The Control Unit must only be opened when it has been ensured that
there is no power to the unit.
Jumper
Delay before pump
Setting
shut-off during top-up
1
2
Jumper setting 1: The pump will turn off 15 seconds after the beginning of a top-up cycle. The
Solenoid Valve will close 1 minute after the water level reaches the Level Probe. If the water level
doesn't reach the Level Probe within 30 minutes the unit alarms.
Jumper setting 2: The pump will turn off 10 minutes after the beginning of a top-up cycle. The
Solenoid Valve will close 20 minutes after the water level reaches the Level Probe. If the water level
doesn't reach the Level Probe within 45 minutes the unit alarms.
TCA5000950 v1.3
Top-up duration after
level probe is reached
15 sec
10 min
www.3ptechnik.co.uk
For larger tanks and flow rates the jumper can be
moved from the default position 1, to position 2. This
position tops up much more water into the tank. (see
below).
In position 2 the pump shut-off delay and alarm
delays are also increased accordingly.
If in any doubt please consult a qualified electrician or
electronic technician.
1 min
20 min
28-Sept-2021
Safety Shutdown delay
30 min
45 min
Page 9 of 12