Operation

Controller/Display
The values will be shown with three digits, and with a setting you
can determine whether the temperature is to be shown in °C or in
°F.
Light-emitting diodes (LED) on front panel
The LED's on the front panel will light up when the relevant relay
is activated.
= Refrigeration
= Defrost
= Fan running
The light-emitting diodes will flash when there is an alarm.
In this situation you can download the error code to the display
and cancel/accept for the alarm by giving the top button a brief
push.
The buttons
When you want to change a setting, the upper and the lower
buttons will give you a higher or lower value depending on the
button you are pushing. But before you change the value, you
must have access to the menu. You obtain this by pushing the
upper button for a couple of seconds - you will then enter the col-
umn with parameter codes. Find the parameter code you want to
change and push the middle button until value for the parameter
is shown. When you have changed the value, save the new value
by once more pushing the middle button.
Examples
Set menu
1. Push the upper button until a parameter r01 is shown
2. Push the upper or the lower button and find that parameter you
want to change
3. Push the middle button until the parameter value is shown
4. Push the upper or the lower button and select the new value
5. Push the middle button again to set the value.
Cutout alarm relay / receipt alarm/see alarm code
• A short press of the upper button
If there are several alarm codes they are found in a rolling stack.
Push the uppermost or lowermost button to scan the rolling
stack.
Set temperature
1. Push the middle button until the temperature value is shown
2. Push the upper or the lower button and select the new value
3. Push the middle button again to conclude the setting.
Reading the temperature at defrost sensor (Or product sensor, if
selected in o92.)
• A short press of the lower button
Manual start or stop of a defrost
• Push the lower button for four seconds.
AK-CC 460
Instructions RI8SE202 © Danfoss 07/2017
Get a good start
With the following procedure you can start regulation very quick-
ly:
1 Open parameter r12 and start the regulation
2 Go through the survey of factory settings. Make any necessary
changes in the respective parameters.
3 For network. Set the address in o03
4 Send address to system unit:
• MODBUS: Activate scan function in system unit
• If another data communication card is used in the controller:
- LON RS485: Activate the function o04
5