Dukane iQ LS-E Uygulama Notu - Sayfa 8
Güç Kaynağı Dukane iQ LS-E için çevrimiçi göz atın veya pdf Uygulama Notu indirin. Dukane iQ LS-E 16 sayfaları. Ultrasonic probe system, automation interface guidelines
DUKANE
Intelligent Assembly Solutions
All System Outputs are optically isolated from the internal circuits and can be connected to sinking or sourcing PLC input
cards. When J3-1 is used to power the outputs, the total maximum output current for all outputs combined is 250mA. If
an external supply is used, as shown in the drawing below, each output can sink or source up to 500mA.
iQ System Outputs
Notes:
1. All System Outputs share the same Isolated Common (J3-24). It is critical that the isolated common is connected
to the positive supply or ground.
2. J3-1 can be used in place of the 24Vdc supply. If so, J3-24 must be connected to J3-3.
AN502 (REV 07)
Page 8 of 16
Connecting System Outputs
PLC Sourcing Input Card
+24Vdc Supply
iQ Digital Outputs
Sinking Current
Isolated Common J3-24
0Vdc Return
APPLICATION NOTE
PLC Input Card
PLC Digital Input
Sourcing Current
AN502