Ayrıca Danfoss VLT FC 103 için: Kullanım Kılavuzu (16 sayfalar), Kurulum Talimatları Kılavuzu (6 sayfalar), Kurulum Kılavuzu (18 sayfalar), Kurulum Talimatları Kılavuzu (8 sayfalar), Kurulum Talimatları Kılavuzu (10 sayfalar), Kurulum Kılavuzu (6 sayfalar), Kullanım Talimatları Kılavuzu (16 sayfalar), Kurulum Kılavuzu (16 sayfalar), Kurulum Kılavuzu (8 sayfalar), Kurulum Talimatları Kılavuzu (6 sayfalar), Kurulum Kılavuzu (6 sayfalar)

Danfoss VLT FC 103 Kurulum Kılavuzu
Installation
3.5.2 Mounting in a VLT
106 Frequency Converter
1.
Remove the lid from the frequency converter.
2.
Check whether the fieldbus option is already
3
3
mounted in the frequency converter. If already
mounted, go to step 4. If not mounted, go to
step 3.
3.
Mount the fieldbus option.
4.
Set the termination switch (shown in
Illustration 3.7) on the fieldbus option to ON,
when the frequency converter is the last station
on the segment.
1
1
Lid
2
®
VLT
3
Connector plug
4
FCP 106
Illustration 3.5 Exploded View
8
®
DriveMotor FCP
4
3
2
PROFIBUS DP MCA 101 option card
Danfoss A/S © 07/2015 All rights reserved.
®
VLT
PROFIBUS DP MCA 101
Illustration 3.6 Option Mounted in FCP 106

3.6 Setting Address Switches

Set the address switches to give the option a unique ID.
Select an address range from 0–125 (factory setting 127)
according to Table 3.1.
Switch
Address
value
5
35
82
Table 3.1 Settings for the Address Switches
Alternatively, assign a unique ID from parameter 9-18 Node
Address. For setting the address from parameter 9-18 Node
Address, ensure that all address switches are set to ON.
When the address is already set using address hardware
switches, the address value shown in parameter 9-18 Node
Address is read-only.
8
7
6
5
4
Not
+64
+32 +16
+8
used
Not
OFF
OFF OFF OFF
used
Not
OFF
ON
OFF OFF OFF
used
Not
ON
OFF
ON
OFF OFF
used
3
2
1
+4
+2
+1
ON
OFF
ON
ON
ON
ON
OFF
MG33C602