Installation Guide | VLT® 24 V DC Supply MCB 107
Table 2: Discharge Time, VLT® HVAC Drive FC 102 and VLT® Refrigeration Drive FC 103
Voltage [V]
Minimum waiting time (minutes)
4
200–240
1.1–3.7 kW (1.5–5 hp)
380–480
1.1–7.5 kW (1.5–10 hp)
525–600
1.1–7.5 kW (1.5–10 hp)
525–690
–
Table 3: Discharge Time, VLT® AQUA Drive FC 202
Voltage [V]
Minimum waiting time (minutes)
4
200–240
0.25–3.7 kW (0.34–5 hp)
380–480
0.37–7.5 kW (0.5–10 hp)
525–600
0.75–7.5 kW (1.0–10 hp)
525–690
–
Table 4: Discharge Time, VLT® AutomationDrive FC 301/FC 302
Voltage [V]
Minimum waiting time (minutes)
4
200–240
0.25–3.7 kW (0.34–5 hp)
380–500
0.25–7.5 kW (0.34–10 hp)
525–600
0.75–7.5 kW (1–10 hp)
525–690
–
1.5 Installing the D-Option
Prerequisites:
The following tools are required for installing the option:
•
Torx 10 screwdriver.
•
Flat-head screwdriver.
Danfoss A/S © 2018.11
7
–
–
–
1.1–7.5 kW (1.5–10 hp) (FC 102 only)
7
–
–
–
1.1–7.5 kW (1.5–10 hp)
7
–
–
–
1.5–7.5 kW (2–10 hp)
Scope of Delivery, Safety, and Installation
15
5.5–45 kW (7.5–60 hp)
11–90 kW (15–125 hp)
11–90 kW (15–125 hp)
11–90 kW (15–125 hp) (FC 102 only)
15
5.5–45 kW (7.5–60 hp)
11–90 kW (15–125 hp)
11–90 kW (15–125 hp)
11–90 kW (15–125 hp)
15
5.5–37 kW (7.5–50 hp)
11–75 kW (15–100 hp)
11–75 kW (15–100 hp)
11–75 kW (15–100 hp)
AN287957936346en-000101 / 130R0308 | 3