Ayrıca Danfoss ECL Comfort 210 için: Kullanıcı Kılavuzu (12 sayfalar), Kullanıcı Kılavuzu (12 sayfalar), Kullanıcı Kılavuzu (6 sayfalar), Kurulum Kılavuzu (4 sayfalar), Kurulum Kılavuzu (20 sayfalar), Kullanım Kılavuzu (10 sayfalar), Kurulum Kılavuzu (7 sayfalar), Kurulum Kılavuzu (16 sayfalar), Kurulum Kılavuzu (16 sayfalar), Kurulum Kılavuzu (16 sayfalar), Kurulum Kılavuzu (16 sayfalar), Kurulum Kılavuzu (20 sayfalar), Kurulum Kılavuzu (16 sayfalar), Montaj Kılavuzu (16 sayfalar)

Danfoss ECL Comfort 210 Kullanım Kılavuzu
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program

2.0 Installation

2.1 Description, in general

Application keys for the ECL Comfort 210 / 296 / 310 series, which
control heating circuits, offer a floor drying program, also called
screed drying program.
The floor drying program is used after a new floor heating circuit
has been placed and fresh-from-factory concrete covers the floor
heating pipes. The floor drying program can also be used, when
the self-leveling screed has been distributed.
The floor drying program can be started immediately in order to
dry-out the concrete / screed according to a set time / temperature
plan.
Navigation to the menu for 'Floor drying':
Common controller > MENU > Floor drying:
Functional heating:
The flow temperature is controlled
according to a set time / temperature plan
in order to dry-out the concrete / screed.
Curing heating:
The flow temperature is controlled
according to a set time / temperature plan
in order to cure the concrete / screed. The
curing must be done before mounting of,
for example, tiles.
Functional and curing heating can work as one process or
separated.
The time / temperature plan is set and is common for selected
circuits.
VI.JM.P2.02
= Time
T
= Functional heating
# 1 #
= Curing heating
# 2 #
© Danfoss | 2017.08 | 5