Ayrıca Danfoss ECL Comfort 210 için: Kullanıcı Kılavuzu (12 sayfalar), Kullanıcı Kılavuzu (12 sayfalar), Kullanıcı Kılavuzu (6 sayfalar), Kurulum Kılavuzu (4 sayfalar), Kurulum Kılavuzu (20 sayfalar), Kullanım Kılavuzu (10 sayfalar), Kurulum Kılavuzu (7 sayfalar), Kurulum Kılavuzu (16 sayfalar), Kurulum Kılavuzu (16 sayfalar), Kurulum Kılavuzu (16 sayfalar), Kurulum Kılavuzu (16 sayfalar), Kurulum Kılavuzu (20 sayfalar), Kurulum Kılavuzu (16 sayfalar), Montaj Kılavuzu (16 sayfalar)

Danfoss ECL Comfort 210 Kullanım Kılavuzu
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program
Prog. execution (Program execution)
Start or stop the floor drying process.
Press and hold the dial for 5 seconds in order to start or stop the
process.
OFF:
The floor drying process is not active
ON:
The floor drying process is active
Max. pwr. failure (Max. power failure period
acceptance)
Setting the max. accepted time for power failure.
If the ECL Comfort controller is without power for more than the set
time, the alarm will be activated when the controller is powered up.
Value: Set the accepted time
The alarm can be reset (MENU > Alarm > Alarm overview)
To restart the floor drying process:
If the parameter "After power fail." (ID 10913) is set to STOP, the
"Prog. execution" must be set to OFF and then to ON.
VI.JM.P2.02
10512
If the ECL Comfort controller is set to manual mode, the floor drying
process can be started, but will not be active.
If "Prog. execution" is set to ON and returns to OFF after 5 seconds,
none of the circuits in the graph (Desired flow T) have been selected
for floor drying.
If the parameter "Appl. continue" (ID 10912) is set to STOP, the "Prog.
execution" remains ON after elapse of the floor drying process.
10514
After a power failure, the alarm is indicated / activated.
If the parameter "After power fail." (ID 10913) is set to STOP, the desired
flow temperature is maintained at the value, set in X1.