Type VPM-VC
(Valve Check)
8.22
Description
The VPM-VC valve test module
checks the tightness of burner gas
shut-off valves in combination with
one or two pressure switches. The
test is performed in accordance with
EN 1643.
The program sequence, filling and
venting parameters as well as pro-
gram times can be adjusted by the
user according to the system require-
ments.
Application
The VPM-VC has been designed for
automatic leak testing between two
solenoid valves in gas-consuming
devices, either prior to start-up or
after switching off the system. The
test system can be used as a single
leakage tester or in combination with
LGV
VPM VC
(NO)
P
p
GW 1
V1
V2
automatic burners. It is used in gas
burner systems for heating, process
heating,
process industry and gas engines.
Approvals
EU type testing certificate as per:
• EU-Gas Appliances Regulation
• EU-Pressure Equipment Directive
The VPM meets the requirements of:
- Machinery Directive 2006/42/EC
- Low Voltage Directive 2014/35/EU
- EMV 2014/30/EU
Approvals in other important gas-
consuming countries.
FM Approvals Class 7610
VPM VC
V3
V2
V4
P
p
GW 1
V1