Test 1: Connect the drive's leads to the corresponding
lead of a suitable current signal source (current calibrator).
Apply power to the actuator, then turn on the current signal
source (current calibrator). Adjust the current signal source
(current calibrator) until the mA meter reading equals the
desired zero point current (2 to 16 mA). Adjust the current
signal source (current calibrator) until the mA meter reading
equals the finish point current. With the desired finish point
current applied, the actuator shaft should drive to the finish
point. If the actuator fails this test repeat the CP-9302-702
Adjustment section. Short the Violet/White wire to the
Violet wire; the actuator shaft should turn counterclockwise.
Short the Violet/White wire to the Bluewire; the actuator
shaft should turn clockwise. When you break the connection
between the Violet/White and Violet wires, the shaft should
return fully clockwise. If the actuator fails this test, perform
Test 2.
TESTING
Test 2: Disconnect the Yellow/Black wire from terminal "X".
Jumper actuator terminal "X" to terminal 2; the actuator shaft
should turn clockwise. When the connection between termi-
nals "X" and 2 is broken, the shaft should remain stationary.
Then jumper terminal "X" to terminal 3; the shaft should turn
counterclockwise. If the actuator passes this test, but failed
Test 1, the side-mounted control box is defective and must
be replaced.
If the unit failed both tests, the actuator itself is defective and
must be replaced. Contact Dungs for replacement informa-
tion.
DIMENSIONS
When replacing a CP 8391-703 control unit with a
CP 9302 702 in NEMA TYPE 4 applications a seal
must be installed into the unused conduit knock out
to maintain NEMA TYPE 4 rating.