Danfoss DHP-R 7UA HPC EM Kurulum Talimatları Kılavuzu - Sayfa 3

Kontrol Ünitesi Danfoss DHP-R 7UA HPC EM için çevrimiçi göz atın veya pdf Kurulum Talimatları Kılavuzu indirin. Danfoss DHP-R 7UA HPC EM 16 sayfaları.

table of contents
Installation for WCS function (warm water loading) . . . 4
Installation for TWC function (tap water control) . . . . . . 6
Installation for Shunt function . . . . . . . . . . . . . . . . . . . . . . . 8
Important information!
24 VAC 1 must not be connected together with:
• 24 VAC 2
• 24 VDC
• Other equipment that uses 0-10V control signal
• Signal ground GND
24 VAC 2 must only be used as power supply to:
• External equipment that requires 0-10V control signal
• Auxiliary modules
The two separate 24 VAC circuits must never be connected
to each other or to protective ground .
The total power load on 24 VAC 1 respectively 24 VAC 2 must
not exceed 50VA.
VMILF102
Danfoss – 3