Beckett NX BURNER TROUBLESHOOTING
Condition 1: Burner motor does not start when there is a call for heat.
Procedure
1. Check that limit switches are closed and
contacts are clean.
2. Check for line voltage power at the oil
primary control. Voltage should be 120
Vac between the black and white lead
wires on the oil primary control.
3. Check indicator light with burner off, no
call for heat (no flame).
4. Shield cad cell from external light.
5. Verify that the oil valve is closed during
the "valve on delay" period by observ-
ing the view port and verifying that no
flame is present during the 15-second
"valve on delay".
6. Jumper thermostat (T -T) terminals on
Aquastat
IMPORTANT
First remove one thermostat lead wire.
OPERATION AND TROUBLESHOOTING
Status
Corrective Action
N/A
N/A
Green Indicator light
Cad cell is defective, sees external light, or connections have shorted. Go to step
is on.
4.
Green Indicator light
Go to step 6.
is off.
Green Indicator light
Eliminate external light source or permanently shield cad cell.
turns off.
Replace cad cell with new cad cell and recheck.
If indicator light does not turn off, remove cad cell lead wires from Aquastat and
Green Indicator light
recheck.
stays on.
If indicator light is still on, replace the Aquastat control.
If the indicator light turns off, replace cad cell bracket assembly.
Green Indicator light
If flame is present, replace the oil valve.
is on.
Trouble is in thermostat circuit. Check thermostat-wiring connections.
Burner starts.
If connections are clean and tight, check thermostat wires for continuity.
•
Burner does not start.
•
If burner still doesn't start, check the oil burner motor. It may be seized or
burned out.
•
Disconnect line voltage power and open line switch.
•
Check all wiring connections.
Tighten any loose connections and recheck.
If burner still doesn't start, replace Aquastat.