BX308 XP Gas Detection Controller
Factory Reset
Warning! Factoy reset erases all user-entered data.
Select "Factory reset", Pressing "ENTER" the writing
starts to flash.
Hold down "ENTER" for 4 seconds, a grid appears with
10 empty rectangles that gradually fill up, at the end of
which the BX308xp is totally reset, and starts a new 90
second warm up countdown.
Relay Expansion cards
Advanced Functions
Up to a maximum of 16 CARD-RLS4 Relay Expansion cards
can be connected to the control unit.
On each board there are 4 auxiliary relays, to be associated
with the desired probe. With a maximum of 64 relays.
The functions related to: Pre-Alarm, Alarm, Fault or not used
can be associated to each selected relay
Each selected relay can be associated with a specific range
of probes from 1 to 16.
CARD-RLS4- Indicates the address set in the card in reading.
Each time the ENTER button is pressed, the
CARD-RLS4 card to be set is selected.
Relay - Each press of "ENTER" chooses the Relay (from 1 to
4) to which you want to associate a function.
Func. With each press of "ENTER" choose the function to
associate: not used-pre-alarm-alarm-failure
PROBE. Each press of "ENTER" chooses the interval of the
sensors to which I must associate the function of the relay
t: 01905 797989
e: [email protected] | w: www.duomo.co.uk
Power
Pre Alarm
Battery
Main Alarm
OL Probes
Exit Alarm
OL Battery
Siren Status
Fault