DANLERS CESRA PIR DSIP Kurulum Notları - Sayfa 2

Anahtar DANLERS CESRA PIR DSIP için çevrimiçi göz atın veya pdf Kurulum Notları indirin. DANLERS CESRA PIR DSIP 2 sayfaları. Pir occupancy switch with dsi dimming

Installation procedure
1. Please read these notes carefully before commencing work.
In case of doubt please consult a qualified electrician.
2. POSITIONING: The CESRA PIR DSIP should be installed to achieve
correct coverage of the area, see diagram A. Avoid locating this product
where it is exposed to drafty conditions (exposed lobbies, open ceiling
voids or near fans) or near heat sources.
3. Make sure the power is isolated from the circuit.
The PIR should be connected as shown in diagram D:
SL
Switched Line out
L
Live in
N
Neutral in
DA -
DSI control line (Polarity independant)
DA +
DSI control line (Polarity independant)
SW
Switch input
1
5. Knockout or drill the appropriate holes on the mounting plate for attaching
the plate to the ceiling or back box (if applicable). Feed cables through
the appropriate (side or rear) entry hole (see diagram E). Screw the back
mounting plate to the ceiling or back box via the mounting holes. Wire the
cables into the sensor head block terminal. Push the sensor head onto the
mounting plate and align the side clips with the slots on the sensor heads.
Start-up mode
When the PIR is powered up, it will switch on the load for 1 minute, the load
will then switch off and the PIR will enter its Operating Mode.
Time / Run-on / Lux set up
The LUX adjuster spindle on the side of the PIR is used to regulate the automatic
daylight linked dimming function lux level (see diagram C opposite). This should
be adjusted in situ by rotating the LUX adjuster slowly anticlockwise (+ to -)
so that the desired level of brightness is achieved under the luminarie(s) being
controlled.
Once the correct level is achieved and there has been no further adjustment to
the LUX spindle, CESR PIR DSIP will go through a 30 second delay before the
automatic closed loop control will start.
CESR PIR DSIP incorporates a fixed 20 second fade rate from maximum to
the set back level.
Sensitivity
CESR PIR DSIP incorporates a sensitivity adjuster, labelled 'SENS', to reduce
the range of detection from 100% to 50% in 9 steps (see diagram B opposite).
A: Detection diagram
For optimum coverage
recommended mounting
height: 2.4 to 5m
up to 5m
up to 7m
B: Adjusting SENSITIVITY and TIME
Typical settings
max
min
max
min
SENS
TIME
100%
50%
40m
10s
20m
20s
10m
40s
5m
80s
2.5m
D: Wiring diagram,
CESRA PIR DSIP controlling several DSI dimmable ballasts
L
230 VAC
N
Mains
rated
retractive
Optional
wall switch
other load
or rocker
wall switch
(toggled)
E: Mounting plate fixing
Knock out mounting
holes or pre-drill
pilot holes.
For cable entry
from above -
knock out central
mounting hole
Strong detection zone
i.e. person moving arm
or walking towards PIR
Secondary detection zone
i.e. person walking
perpendicular to PIR
C: Adjusting LUX and RUN-ON
Typical settings
max
min
max
LUX
INFINITE
30m
20m
15m
DSI
DSI
Ballast
Ballast
DSI Control Lines
L
SW
CESRA PIR DSIP
CEFLA PIR DSIP
1
N
SL
Join device to
mounting plate via
mounting clips
For side entry -
knock out side
mounting hole
Connect wires to
from mounting
terminal block on
plate and device
the device
min
RUN ON
0s
1m
2m
5m
10m