DANLERS TLSW 10 Kurulum Notları

Anahtar DANLERS TLSW 10 için çevrimiçi göz atın veya pdf Kurulum Notları indirin. DANLERS TLSW 10 2 sayfaları. Plated time lag switches (2-wire versions)

DANLERS TLSW 10 Kurulum Notları
Troubleshooting
Time lag switch can not be re-triggered instantly:
• Small non-resistive load (Contactor, CFL, LED or 2D lamps).
Add one CAPLOAD per TLSW 10 (ILM) across the load,
as shown in wiring diagrams.
Slave switch does not operate the time lag switch:
• Ensure only DANLERS slave switches are used.
• Ensure slave wiring is less than 10m long.
Does not work with existing 2-way switches:
• Time lags and slaves can use the wiring of 2-way switching
circuits, but not be mixed with 2-way switches.
Output always live:
• Time lag operated within 30 seconds of connecting the supply.
Release latched relay with firm sideways knock to product with a
small blunt object such as a screwdriver handle.
Precautions and Warranty
This product conforms to BS EN 60669-2-1.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided e.g. 6 amps over current, 1kV over voltage. Please ensure
that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
16/03/12
DANLERS 2-wire plated time lag switches do not need a neutral and
are suitable for replacing standard wall switches or pneumatic time
lag switches. The wall box must be at least 16mm deep.
A short press will switch the load on and it will switch off automatically
after the time lag period has expired. The time lag can be set between
approximately 1 and 10 minutes.
The button on the illuminated version (TLSW 10 ILM) is lit until the
button is pressed. It comes back on when the time lag has elapsed.
The load can be switched on from other locations by connecting
these devices in parallel or by connecting DANLERS matching slave
switches, available as both a plated single gang slave (SS 1SL) and
a two gang slave (SS 2SL).
These switches should only be connected to 230V 50Hz AC.
They can switch up to 6 amps (1500W) of:
• Fluorescent lamps, either high frequency or switch start
• Incandescent or mains halogen lamps
• Electronic or wire wound transformers.
They can also switch up to:
• 2 amps (500W) of Compact fluorescent, LED and 2D lamps.
• 1 amp (250W) of Fans or Metal Halide lamps.
Larger loads can be switched via contactor. (Also see below)
Because there is no neutral connection there is a minimum load
requirement of 40W RESISTIVE for each TLSW 10 (ILM) in the circuit.
If the load is less than this or is not totally resistive, i.e. a contactor, CFL,
LED, 2D lamps or emergency fitting, then one power factor correction
capacitor, CAPLOAD, needs to be added across the load for each
TLSW 10 (ILM) in circuit, as shown in the wiring diagrams overleaf.
INS983 TLSW 10
Plated time lag switches (2-wire versions)
TLSW 10
TLSW 10 ILM
Loading
Minimum load

Installation notes

(recommended with integral safety fuse)