DANLERS COPD Kurulum Notları - Sayfa 2
Güvenlik Sensörleri DANLERS COPD için çevrimiçi göz atın veya pdf Kurulum Notları indirin. DANLERS COPD 2 sayfaları. Compact person detector, pir switch
Ayrıca DANLERS COPD için: Kurulum Notları (2 sayfalar)
Installation procedure
1. Please read these notes carefully before commencing work.
In case of doubt please consult a qualifi ed electrician.
2. The detector should be sited so that it is not shaded from daylight
3. The detector should be mounted between 1 and 2.2 metres high, via
any of the four pre-drilled mounting holes only.
4. It must be mounted with the cable entering from below.
5. Make sure the power is isolated from the circuit.
6. The detector should be connected as shown in diagram E
L - Live in, N - Neutral in, SL - Switched Line out.
7. IMPORTANT - Replace terminal cover.
8. Once the wiring has been completed and verifi ed, switch on the supply
and test the operation.
Lux and Time set-up
For convenience, ensure that the TIME is set to minimum when setting up
the LUX level. Afterwards set the TIME to a value suitable for the application.
8. When powered up, (after 1 minute stabilisation time) turn lux pot
(diagram C) fully clockwise and time pot fully anticlockwise.
9. Press the MODE button (diagram B) for approximately 0.5s. The
LED will go green indicating the LUX cell is active. (Or press and
hold button for approx. 4 seconds – LED goes RED indicating Lux
cell INACTIVE). Repeating these steps will toggle the functionality.
10. If lux cell active, vacate area until PIR switch switches the load off
(should be after 10 seconds).
11. With the LUX as desired on working plane from daylight ONLY (no
artifi cial light), wind the lux pot anticlockwise whilst waving your
hand in front of the PIR cell. When the PIR switches the load ON,
stop turning the pot. The Lux inhibit level is now set.
12. Turn the PIR time to the desired timeout (diagram D). Whenever a
person is detected, the time lag will start again and the load will stay
switched on.
Precondition
Power-up Condition
Lux Cell Inactive
Lux Cell Inactive
Relay OFF
Relay comes ON for 1 Min. After 1 min. ready for detection.
Lux Cell Active
Lux Cell Active
Relay ON
Relay stays ON for 1 Min. After 1 min. ready for detection.
Lux Cell Active
Lux Cell Active
Relay OFF
Relay comes ON for 1 Min. After 1 min. ready for detection.
Lux Cell Inactive
Lux Cell Inactive
Relay ON
Relay stays ON for 1 Min. After 1 min. ready for detection.
A: Detection range
Recommended mounting
height 1 to 2.2 metres
Strong detection zone
(5m) i.e. person walking
towards detector
B: Time/Lux adjusters (inside casing)
2.5m
80s
5m
Dual colour LED:
40s
10m
RED - PIR active,
STATUS
MODE
20s
Photocell inactive
20m
GREEN - PIR and
10s
40m
Photocell override ON
(passive LUX)
min
max
TIME
Time
Delay
10
Spindle
1000
TIME
LUX
D: Time adjustment
E: Wiring diagram
Inside detector housing
2.5m
L
80s
5m
optional manual
40s
10m
wall switch for
overriding off
20s
20m
10s
40m
230 VAC
min
max
N
TIME
Safety cap
Locate safety cap plastic
pins in the hole 'L' and
second 'N' holes above
the termination screws.
Press firmly to attach.
Secondary
detection zone
(10m, 8m at
extremes)
i.e. person
walking
perpendicular to
detector
C: Lux adjustment
Lux Cell
Mode
1000 LUX
max
min
LUX
Lux
Setting
Use Mode Button to disable
Spindle
LUX (see diagram B)
COPD or COPD BK
SL
N
1000 LUX
10 LUX
max
min
LUX
10 LUX
load