Belimo FS Series Talimatlar Kılavuzu - Sayfa 20

Motor Belimo FS Series için çevrimiçi göz atın veya pdf Talimatlar Kılavuzu indirin. Belimo FS Series 20 sayfaları. Replacement of multiproducts motors
Ayrıca Belimo FS Series için: Değiştirme (19 sayfalar), Talimat Sayfası (18 sayfalar)

Belimo FS Series Talimatlar Kılavuzu

Building Official / Fire Marshal Notification Form

Retain this portion of checklist at premises for inspection. See local AHJ for other information and
requirements regarding conformance with NFPA 80 & NFPA 105.
Test Checklist (Smoke dampers do not have sensors. Only steps a & b apply.)
1. Fusible Link Combination Damper
a.  Open smoke detector or relay wire or contact to cut power. Damper springs closed.
b.  Reconnect power. Damper drives open.
c.  Unhook fusible link. Replace if broken. PROTECH HANDS. Damper springs closed.
d.  Reopen damper and rehook fusible link.
e.  Repeat steps a. and b. Damper drives open.
2. Reopenable Two Sensor Fire-Smoke Combination Damper
(Since this system involves the Firefighters' Smoke Control System, inform fire department in all
cases.)
The sequence will be similar to that described below. After the above test perform the tests below.
With FSCS switch in Auto position:
a.  Disconnect power from smoke detector or relay contacts. Actuator springs damper closed.
b.  Reconnect power. Actuator drives damper open.
c.  Trip thermal sensor. Actuator springs damper fully closed.
d.  Press manual reset. Actuator drives damper open.
Test FSCS switch functions:
a.  Move FSCS switch to Off position. Actuator springs damper fully closed.
b.  Move FSCS switch to Hand position. Actuator drives damper open.
c.  Trip secondary (higher temperature) thermal sensor. Actuator springs damper fully
d.  Press manual reset of secondary sensor. Actuator drives damper open.
Move FSCS switch back to Auto position:
a.  Actuator springs damper closed if Primary sensor is still open.
b.  Actuator stays open if Primary sensor has re-closed.
When completed, ensure sensors are reset and smoke detector is in normal state and FSCS
switch is in Auto. Damper is normally Open; check sequence of operation.
Damper Numbers or Location Identifying Numbers.................................................................
Date......-............-........
Contractor......................................................................................................................
Service Technician (Print)..................................................................................................
Service Technician (Signed)...............................................................................................
Phone Number (......)......................................................
Notes............................................................................................................................
....................................................................................................................................
....................................................................................................................................
Greenheck MP2985 & MP2986 Motors with Belimo FSxx Series
January 2015
closed.
20