LOCKING
LOCKING
BAND RECESS
TAB
VERIFY GASKET IS
SEATED IN FEMALE
END OF PIPE
LOCKING
BAND CLASP

JOINT CONNECTIONS

Verify the gasket is seated evenly inside the
groove in the female end. For PP / Metal
pipe with a locking tab, slide Locking Band
on male pipe section Fig.2. Insert locking
tab into locking band recess, rotate button
away from Locking Band Clasp, insert pipe
sections, push lock band clamp downward
into socket, disengage socket / tab 1/4"-5/8"
from socket Fig.2. Screws are not allowed
for joint connection. Never penetrate the
wall of PolyPro vent pipe. (Exception- a SS
screw may be used outside the building on
exterior termination fittings to orient an
elbow, etc).
IMPORTANT: Locking bands are
mandatory on all exhaust vent joints
POLYPRO TO DURAVENT / SECURITY
CHIMNEY METAL VENT CONNECTION
Approved M&G Duravent / Security Chimney
1738/636 metal vent fittings can be used with
PolyPro. Follow the above (Fig.2) for PolyPro
(female) to Metal Vent (Male) connections.
6
CLICK!
Figure 2

APPLIANCE CONNECTION: 2" - 4"

1.
If the appliance has a PVC/CPVC female
outlet use the Appliance Adapter/ PVC
Adapter and Clamp. (Fig.3)
If the appliance has a PVC/CPVC
Male outlet use a matching PVC/
1/4"
CPVC coupling to convert to a
female outlet.
2.
If the appliance outlet has a rubber
boot or Fernco-style appliance adapter,
then the PolyPro vent pipe may attach
directly to the appliance (Fig.4).
3.
If the appliance has a FasNSeal outlet
then use the FasNSeal to PolyPro
adapter.
POLYPRO PIPE
APPLIANCE
ADAPTER CLAMP
APPLIANCE ADAPTER/
PVC ADAPTER
APPLIANCE
EXHAUST OUTLET
OR PVC UNION
APPLIANCE
Figure 3
POLYPRO
VENT PIPE
TIGHTEN CLAMPS ON
RUBBER COUPLER
ADAPTER OR FERNCO
STYLE ADAPTER TO
SECURE VENT
PIPE TO APPLIANCE
APPLIANCE
OUTLET
Figure 4