DuraVent DIS4 Manuel - Sayfa 10

Havalandırma DuraVent DIS4 için çevrimiçi göz atın veya pdf Manuel indirin. DuraVent DIS4 20 sayfaları. Ul 1978 - grease duct professional series kitchen ventilation

SECTION D – PIPE & FITTING JOINT
ASSEMBLY
The ends of each inner pipe are made of flanges (1/2"). All the
joints between sections are a flange-to-flange connection of
the inner pipe.
SPECIAL FEATURE
All sections have an unattached "Alignment Sleeve".
The alignment sleeve facilitates centering of adjacent sections
and provides backing for the sealant applied to the flange
keeping the sealant in the intended location. Typically, it is
inserted in the downstream end but may be removed.
Although not required, it aids in easier assembly, better sealing
and adds strength to the section joint
Figure 11: Feature of the Alignment Sleeve
JOINT ASSEMBLY
STEP 1:
Fill the channel of the inner V-band with S-650 sealant
supplied by DuraVent and place below the flange of the first
section.
Figure 12: Joint Assembly Step 1
STEP 2:
Apply a small continuous bead of S-650 sealant approximately
3/16" wide to one of the flanges to be joined.
Figure 13: Joint Assembly Step 2
10
CIXPRO SERIES FOR GREASE DUCT UL1978 SUBMITTAL RECORD
STEP 3:
Join the two flanged ends of the duct section together and
rotate slightly to ensure complete coverage of the sealant on
flanges.
Figure 14: Joint Assembly step 3
STEP 4:
Install the V-band around the flanges making sure the flanges
are located within the V-Clamp.
NOTE: do not locate V-band hardware at the bottom
side of horizontal ducts
NOTE: light tapping with a hammer all around the
band while tightening bolts helps align and pull
flanges together.
Figure 15: Joint Assembly step 4
STEP 5:
Install the supplied AES insulation strips between sections to
ensure that all gaps are filled. Be sure that insulation is tightly
packed and completely fills the void between flue and closure
band when assembled
Figure 16: Joint Assembly step 5
STEP 6:
Secure the Outer Casing with the Outer Band (BSE).
Joint installation is complete.
REV: 0
AUGUST 2017
10