DuraVent DIS4 Manuel - Sayfa 2

Havalandırma DuraVent DIS4 için çevrimiçi göz atın veya pdf Manuel indirin. DuraVent DIS4 20 sayfaları. Ul 1978 - grease duct professional series kitchen ventilation

Models: DCL, DAS1, DIS1,
DIS2, DIS4, DIS3Z
SECTION A – CODE COMPLIANCE
UNDERWRITERS LABORATORIES
LISTINGS
Model DCL (single wall) DAS1 (1-inch air), DIS1, DIS2, DIS4, DIS3Z
(Double wall, AES Insulation)
UL 1978 - Grease Duct – All Models
UL 2221 - Fire Resistant Enclosure DIS3Z ONLY
ULC S662 - Grease Duct – All Models
COMPLIES TO THE FOLLOWING:
National Fire Protection Association (NFPA)
Complies with NFPA 96 – "Standard for Ventilation
Control and Fire Protection of Commercial Cooking
Operations
International Code Congress (ICC)
Complies with "International Mechanical Code" and
"International Building Code" if applicable to the
project or site
International Association of Plumbing and Mechanical
Officials (IAPMO)
Complies with "Uniform Mechanical Code" if
applicable to the project or site
UL 1978 Grease Duct Listing:
DuraVents
Model
DCL,
and DIS3Z are listed for continuous temperatures of 500°F
and intermittent temperatures of up to 2000°F, and are
ideally suited for use in commercial cooking installations
for the removal of smoke and grease laden vapors (Type I
or Type II kitchen exhaust hood). Grease duct system
size and capacity information may be obtained from the "
ASHRAE Handbook – Fundamentals " or from the "
Air
Pollution Engineering Manual " of the " US
Environmental Protection Agency. "
2
CIXPRO SERIES FOR GREASE DUCT UL1978 SUBMITTAL RECORD
5"- 36" ID
5"- 36" ID
5"- 36" ID
DAS1,
DIS1,
DIS2,
DIS4
ULC S662 - Grease Duct
These requirements cover factory-built grease ducts and
grease duct assemblies that are intended to be installed as
alternatives to the grease ducts constructed of all welded 1.37
mm carbon steel or 1.09 mm stainless steel required by ULC-
S650, Standard for the Installation and Performance of
Ventilation and Fire Suppression Systems for Commercial
and Institutional Cooking Equipment. Grease ducts covered
by these requirements are intended to be installed in a fire
rated enclosure when required by the provincial or territorial
regulations or bylaws, or in the absence of those
requirements by the National Building Code of Canada.
Grease duct assemblies that penetrate fire rated assemblies
which do not require the protection of a fire rated enclosure
are covered by the requirements contained in CAN/ULCS144,
Standard Method of Fire Resistance Test - Grease Duct
Assemblies.
UL 2221 Listing:
DuraVents Model DIS3Z is classified in accordance with
UL 2221 (Tests of Fire Resistive Duct Enclosure
Assemblies) as an alternate to a 2-Hr. fire resistive shaft
enclosure with a minimum zero clearance to combustibles
(sizes 5" to 36" diameters). Model DIS3Z has been
evaluated in accordance with the requirements for duct
enclosure Condition A.
MIXING PARTS
Model DCL, DAS1, DIS1, DIS2, DIS4 and DIS3Z
listed to UL 1978 may be intermixed within a system,
assuming proper clearances are maintained for
respective components. When penetrating a roof,
appropriate roof penetration components must be
used.
Do not use Model DCL to penetrate through a
wall, floor or roof.
REV: 0
AUGUST 2017
2