Load refers to any item that limits current (PLC input, ice cube relay, etc.) that you would like the M100
to switch on/off. Load must be the same voltage rating as the supply being used. Total circuit current
is 50 mA (max).
L
STOP
The relay is held in during normal operation.
If the shaft stops rotating, the relay will drop
out and the motor will shutdown.
1. Check that the unit is correctly installed (see standard wiring diagram).
2. Check that the distance between the target, stud or bolt head and sensing face of M100 Stopswitch is
within the minimum distance specified.
3. Start up machine.
4. The unit is now set. If the M100 Stopswitch fails to receive a signal within every 4 second period, (i.e.
target stops rotating or there is a power failure) the unit will switch to normally open.
5. Test by sliding a metal putty knife between the sensor and the target.
6. During normal operation the blue LED will flash each time an input signal is received. The closed circuit
is indicated by a permanent green LED. If the unit fails to receive a signal for 4 seconds the circuit
reverts to open state indicated by the green LED going out.
If the system does not immediately shutdown as expected or alarm as required, then remove the
machine from service until the problem has been diagnosed and corrected.
INCORRECT
Black (N / 0V)
Supply
24 to 240
Volts AC/DC
Blue (L / +V)
NOTE
TYPICAL CONTROL WIRING
START
CTR
TESTING AND COMMISSIONING
WARNING
x
R
Blue
M100
PAGE 9
CTR
Black
R
N