Wiring Details
All wiring terminals will accept solid or stranded cables up to 2.5mm²
RELAY CONTACT 1
1A at 30V MAX 30V AC or DC
L1
L2
+
-
-
+
+
+
L1 and L2 are polarity sensitive
L1
L2
XP95 LOOP
Current consumption at 28V (no protocol)
LED Enabled
switch-on surge 160ms
quiescent
relay operated
relay operated (LED disabled)
For a full technical specifi cation of the Output Unit, please refer to the Output Unit PIN Sheet,
PP2093. For further information on isolators, please refer to PP2090.
N/C COM N/O
N/C
COM
N/O
4mA
500μA
1.8mA
600μA
2
Address Setting
The address of the Output Unit is set using the lower seven segments of the DIL switch. Each
segment of the switch must be set to "0" or "1", using a small screwdriver or similar tool. A
complete list of address settings is shown below.
DIL switch
addr
setting
ting
1234567
1
1000000
2
0100000
3
1100000
4
0010000
5
1010000
6
0110000
7
1110000
8
0001000
9
1001000
10
0101000
RELAY
51
1100110
CONTACT 2
52
0010110
1A at 30V
53
1010110
MAX 30V AC
or DC
54
0110110
55
1110110
56
0001110
57
1001110
58
0101110
59
1101110
60
0011110
101
1010011
102
0110011
103
1110011
104
0001011
105
1001011
106
0101011
107
1101011
108
0011011
109
1011011
110
0111011
Commissioning
It is important that the Output Unit be fully tested after installation. An XP95 Test Set, part no
55000-870, may be used to carry out functional testing of individual units. It can also be used to
perform data integrity tests of an entire loop.
Note: If this product has been subjected to excessive shock during transportation, it may be
received with the relay contacts in the 'set' position. Reset the relay by subjecting it to one
operating cycle before commissioning the system.
LED Indicators
Isolator
Relay On
The use of the red LED can be disabled by setting the 'LED ENABLE' segment of the DIL switch
to '0'.
DIL switch
DIL switch
addr
setting
addr
setting
1234567
1234567
11
1101000
21
1010100
12
0011000
22
0110100
13
1011000
23
1110100
14
0111000
24
0001100
15
1111000
25
1001100
16
0000100
26
0101100
17
1000100
27
1101100
18
0100100
28
0011100
19
1100100
29
1011100
20
0010100
30
0111100
61
1011110
71
1110001
62
0111110
72
0001001
63
1111110
73
1001001
64
0000001
74
0101001
65
1000001
75
1101001
66
0100001
76
0011001
67
1100001
77
1011001
68
0010001
78
0111001
69
1010001
79
1111001
70
0110001
80
0000101
111
1111011
121
1001111
112
0000111
122
0101111
113
1000111
123
1101111
114
0100111
124
0011111
115
1100111
125
1011111
116
0010111
126
0111111
117
1010111
118
0110111
119
1110111
120
0001111
Illuminated yellow when a short circuit on the loop causes the
integral isolator to operate
Illuminated red when relay is energised
3
DIL switch
DIL switch
addr
setting
addr
set-
1234567
1234567
31
1111100
41
1001010
32
0000010
42
0101010
33
1000010
43
1101010
34
0100010
44
0011010
35
1100010
45
1011010
36
0010010
46
0111010
37
1010010
47
1111010
38
0110010
48
0000110
39
1110010
49
1000110
40
0001010
50
0100110
81
1000101
91
1101101
82
0100101
92
0011101
83
1100101
93
1011101
84
0010101
94
0111101
85
1010101
95
1111101
86
0110101
96
0000011
87
1110101
97
1000011
88
0001101
98
0100011
89
1001101
99
1100011
90
0101101
100
0010011