Duro Dyne DuroZone RED-4 Kurulum Talimatları Kılavuzu - Sayfa 4
Kontrol Sistemleri Duro Dyne DuroZone RED-4 için çevrimiçi göz atın veya pdf Kurulum Talimatları Kılavuzu indirin. Duro Dyne DuroZone RED-4 16 sayfaları. Zone control system
Selecting use of Zone4 Damper
Dip switch #9 selects whether Damper4 is being used as
Zone4 damper or as a fresh air damper. When it is used as
a fresh air damper, the minutes per hour of fresh air is set
on the panel.
Selecting One-Zone Operation
the panel can be operated as a single (one-zone) system.
the panel will control all the dampers together based on the
Zone1 thermostat.
this can eliminate the need to change all the thermostats
when the home or building is vacant such as at night or
during vacation periods.
One-Zone operation can be selected using the 1ZnE switch
on the panel or an external switch. the LED adjacent to
the switch will be activated when One-Zone operation is
selected.
Emergency Heat Operation
Emergency Heat can be selected from Zone 1 when using
a heat pump thermostat. When using a conventional heat/
cool thermostat the Emergency Heat can be selected on
the panel switch or an external switch. If emergency heat is
activated by the panel switch or an external switch, the LED
adjacent to the switch will be lit. Any heating calls from any
thermostat will be treated as emergency heat calls.
the emergency heat switch on the panel or an external switch
cannot be used when Dip switch #4 is set to heat pump
thermostat. the emergency heat switch on the thermostat
must be used in this mode.
If an emergency heat call is initiated by a heat pump thermostat
in Zone1, an emergency heat call will occur. the panel will
treat all calls for heating as emergency heat calls until Zone1
calls for a non-emergency heat call or a cooling call.
Timer Reset Switch
Momentarily pressing the timer Reset switch clears the
built-in timers allowing the system to be checked out more
quickly.
DuroZone
RED4 - InStALLAtIOn InStRUCtIOnS PAGE 4
RED4 InstrManual-7-1-10.indd 4
24VAC Power
24VAC is connected to the panel at the terminals marked
24VAC. A 40VA transformer should be used and the
output connected to terminals 1 and 2 (not polarized). A
circuit breaker type fuse is located next to the terminals. If a
short should occur in the damper or thermostat wiring, the
Fuse will open the circuit and then close the circuit when the
short is removed.
WARNING! THE FuSE GETS VERY HOT WHEN
A SHORT OCCuRS AND SHOuLD NOT BE
TOuCHED.
PLEASE NOTE: YOu MuST uSE AN INDEPEN-
DENT LOW VOLTAGE POWER SuPPLY.
Heating Limit Potentiometer
this potentiometer sets the maximum Supply Air Plenum
temperature allowed in heating. A low cost Supply Air
1ZNE
Sensor can be used to monitor the temperature and if the
supply air temperature exceeds the set Heating Limit, the
EXTERNAL
SWITCH
heat is turned off and the indoor fan is activated. After two
minutes the heat will be turned back on if the supply air has
R
dropped below the Heating Limit.
Cooling Limit Potentiometer
this potentiometer sets the minimum Supply Air Plenum
temperature allowed in cooling. If the supply air temperature
drops below the set Cooling Limit, the cooling is turned off
and the indoor fan is activated. After two minutes the cooling
will be turned back on if the supply air has risen above the
Cooling Limit.
W2/E
EXTERNAL
SWITCH
R
W2/W3/Y2 Timer Potentiometer
Second and third stage heating and second stage cooling
are controlled by a timer. If the panel has been calling for
heating or cooling longer than the time set on the W2/
W3/Y2 timer potentiometer, the second stage heating
or cooling will be activated provided it is not inhibited by
the Outdoor temperature Limit or the Capacity Limit. If
the panel has been calling for second stage heating longer
than the time set on the W2/W3/Y2 timer Potentiometer,
the third Stage Heating will be activated provided it is not
inhibited by a limit.